ATTENTION!!!
CAUTION : Do not view directly with bare eyes.
923100405_09_001
923100405_09_001
4
5
Non Maintained operation: The luminaire lights its illumination source, only in mains power supply’s
failure.
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the
mains power supply or not.
NOTE!!
The installer should fill in, on the specification label, the letter
G
if the luminaire is used as a
safety sign.
European
manufacturers
Olympia Electronics - European manufacturer
Thank you for your trust in our products
Warranty
Manual Test
Lens Removal
2
2
1
3
1
NOTE!
! The light source is non-user replaceable.
The light source contained in this luminaire shall only be replaced by the manufacturer, or
his agent, or a similar qualified person.
2
2
1
1
4. Replace the removed parts (previous steps 1 and 2).
3. Remove the old battery and place a new one of the same type and characteristics.
2. Follow step 2 of the installation instructions and remove the reflector.
1. Follow step 1 of the installation instructions and remove the diffusor.
It can be done only by a competent person and after the mains interruption
.
Battery Replacement
OLY-1004/WL
WATERPROOF SELFTESTING
MAINTAINED/NON MAINTAINED
EMERGENCY LUMINAIRE
IP42
Non
maintained
NM
25m
Maintained
Μ
350/295/95lm
Light output
1h/3h/8h
Duration
Wireless
OLY-1004/WL
Olympia Electronics S.A.
10-12V DC
1h: 2W
3h: 1.6W
8h: 0.6W
2701205
50 °C max. across the board
Non reversible connection between main pcb and led module
Warranty
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed
to them in writing. Products that have been damaged can be returned to the premises of our company for
repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
Warranty
LED Characteristics
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
CONNECTIONS
NOMINAL POWER
TEMPERATURE (tc)
OLY-1004/WL
220-240V AC / 50-60Hz
4.5W / 4.7VA
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
3.6V/3 Ah
0.95
BATTERY (Ni-Cd)
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
MINIMUM POWER FACTOR
WIRE CROSS SECTION
MAX OPEN CIRCUIT VOLTAGE
Irated
Prated
U-OUT
SUPPLY CURRENT
Basic insulation
1h: 2W
3h: 1.6W
8h: 0.6W
1h: 174mA
3h: 145mA
8h: 47mA
22V
22V
19mA
2
2
0.5mm - 2.5mm
BATTERY PROTECTION
28 white LEDs
1 h, 3 h, 8 h
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
24 hours
LED Charge, Lamp Fault LED, Battery Fault LED
IP42
25m
VIEWING DISTANCE (as safety sign)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
o
5 to 40 C
ABS/PC, PC
770gr.
270 x 147 x 48 mm
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
Up to 95%
3 years (1 year for the battery)
INDICATIONS
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
1h: 510-885mA
3h: 410-715mA
8h: 138-220mA
190-210mA
100mA
MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
MIN MAX. CHARGE CURRENT
TRICKLE CHARGE VOLTAGE/CURRENT
MAX CHARGE VOLTAGE
3-4.5V
6V
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
300lm / 350lm (1 h), 295lm (3 h), 95lm (8 h)
CONTROL GEAR MAX. TEMPERATURE:tc
o
50 C at R18/R19
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2,
ΕΝ 61000-3-3, ETSI EN 303 446-1 v1.1.0, ETSI EN 300 220-2 v3.1.1
Tx POWER
Tx/Rx FREQUENCY RANGE
11dBm
868-870MHz
480:
8 hours duration
180:
3 hours duration
60:
1 hour duration
G:
Internally illuminated safety sign
F:
Automatic test gear complying with IEC 61347-2-7 denoted EL-T
C:
Including inhibiting mode
B:
Including remote test mode
A:
Including test device
1:
Maintained operation
(*)
X:
Self contained
LABELING EXPLANATION:
NOTE:
LED= Light Emitting Diode
X 1
6 0
A
F
B C
G