Use a certified electrical box 250V
AC (IP40) to
perform the electrical connection, with minimum
internal space
35
x
35
x
25
mm to install the 3 pole
terminal block. In this box install a certified 3 pole
terminal block 250V
AC/16A
2,5
mm²
providing
terminals to connect the live wire L,
the neutral
N
and the ground
GND. To this terminal block is
connected the power cable with a cross section of
1,5mm². Install the electrical box in an appropriate
area in the ceiling
.
Install securely the 3 pole
terminal block and perform the connection according to figure 3.
The electrical box and the 3 pole terminal block are not provided by olympia electronics.
Electrical box
(Not included
)
Figure 2
ELECTRICAL BOX INSTALLATION
1.
Attention
!!!
Interrupt the mains power supply
.
2
.
Perform the preparation procedure for ceiling mounting on
page
2
and exclude step 4
.
3.
Perform the procedure for ceiling mounting figure
1.
4.
For the installation of the electrical box you may need to
open holes in the ceiling and at it’s cable entrances, for the
entrance of the power and illumination sign’s cables. Install the electrical box next to the sign so as to
cover the cable (figure 2
).
3.
After mounted the electrical box open the cover and perform the electrical connection according to
Figure 3. After the connection close the
cover
of the box.
4.
Power the illumination sign and check the illumination sign’s operation
.
OPTIONAL
!!
When a triple core cable must be used, then follow the figures 2,3 bellow.
220-240V
AC/50-60Hz
BLUE
L
GND
N
BROWN
Electrical
box
Figure
3
2.
Place the plastic part
1.
Open the pre-etched knock out and pass the
cable thru
.
3. Place the cable holding accessory and mount it by
tightening the screw with the included grommet.
5. Place the mounting accessories in the wall
and tighten the mounting screw figure 1 step 3.
6. Place the plastic cover.
Wall in bottom view
Wall mounted installation
using the special mounting
brackets contained in the
package.
4.
Connect the wires to the included terminal block and
place it in the plastic mounting part
.
Wall mounting