Installation methods
Wall mounting
Luminaire disassembly
3
2
1
Ενδεικτικά
1
2
Insert the
power cable
Insert the
cable grommet
Insert the
cable grommet
Insert the
power cable
Insert the
power cable
Insert the
power cable
Insert the
cable grommet
Ceiling mounting
1
1
1
1
1
1
Luminaire
Set of Pictograms
Manual
Package contents
General
Hanging installation
Wall mounting accessories
Ceiling mounting accessories
2.
The device must be connected to the mains power
supply through a fuse that is dependent on the total
line’s power load.
Resetting errors
3.
In case of battery replacement, this must be
replaced by part of the same type, by the
manufacturer or by a competent person.
4.
In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
Automatic Autonomy Test
1.
Operations for installation, maintainance or
testing must be done by authorized personnel only.
Connectors
The luminaire has the ability to be connected to
GR-6500 panel. In order to do so, the luminaire’s
address has to be unique in the same bus. For
more information, see the extra brochure.
Push the test button for more than 10 seconds, to
delete all the LED indicated errors. Then the device
enters regular operation mode.
CN10:
Power connector
6. It is not allowed to discard batteries into
common trash bins, they must be discarded
only in battery recycling points. Do not
incinerate.
5.
The control gear is not proof against supply
voltage polarity reversal.
CN11:
Communication Port
Addressable Communication
ΑΤΤΕΝΤΙΟΝ!!!
CN6 & CN7:
Battery connector
The Automatic Autonomy Test is conducted every 6
months and measures the device’s back up operation
and emergency duration. This test includes all
functions of the Manual Autonomy Test.
CN5:
Non user connector
CN9:
Module Port
CN7:
Recess LED Port
o
These luminaries are used indoors (ta 40 C) where
emergency light is needed. Each luminary must be
permanently connected to mains power supply. In
normal operation the led strip lights and the battery
is charging. In case of a mains power supply
failure the luminary will light the led strip
automatically in emergency mode (powered by its
battery). When the mains power supply is restored
the device turns to normal operation.
Manual test for emergency operation and light
source.
The manual test can be conducted only if the mains
power supply and the battery is connected:
During the Test the lamp fault LED blinks.
This test includes all the operations that provide the
manual test and is conducted automatically every 15
days. In order to be performed, the mains power
supply and the battery should be connected.
Automatic Operational Test
Manual Autonomy Test
A duration test can be conducted if the TEST button
is pressed from 5 to 10 seconds. The luminary enters
emergency mode, the charge LED is turned OFF and
the Battery Fault led starts to blink. The test is
conducted until the battery is depleted.If at the end
of the test the autonomy is low then the Battery
Fault LED will be ON. If the result of the test is good
then the luminary enters charging mode and the
Charge led starts to blink until the batteries are fully
charged.
Description
Indications LED Status
BATT.
FAULT
(yellow)
LAMP
FAULT
(red)
CHARGE
(green)
Fully charged
Charging
Battery fault or
emergency mode
Operational test
Light source fault
Autonomy test
Duration fault
Note:
Permanently
ON
Blink
Indifferent
Off
After the desired installation follow the steps below
1
L
B
N
A
Insert the signal
cable
Insert the
power cable
2
Battery Connection
ON
1 2 3 4
Maintained operation
ON
1 2 3 4
Non-maintained operation
N
L
Power Connection
Ν
for neutral,
L
for live wire
A
A
B
B
Communication Connection
Pass the 2 signal cables and connect them
on the A, B terminals minding the correct
polarity. These cables are used to connect
the luminaire to GR-6500 panel.
DS1
1h
ON
1 2 3 4
3h
(default position)
ON
1 2 3 4
8h
ON
1 2 3 4
Changing the operating mode
The user can select one of the 3 available minimum autonomy durations 1 hour, 3 hours and 8 hours. The
selection must be done while the luminaire is disconnected from AC and battery supplies. The selection is
achieved through Switches 2 & 3 of DS1. Switch 1 is not used.
The control of maintained or non maintained operation of the luminary is achieved through Switch 4 of DS1.
For maintained operation, switch number 4 must be in ON position. For non-maintained operation, switch
number 4 must be in OFF position.
Technical label installation
Autonomy duration selection
Two additional labels are included in the package. one for 1 hour duration (60) and one for 8 hour duration
(480). Depending on the selected duration, the installer must cover the default 3 hour (180) printing with one
label that has the required duration. Please take notice of the orientation of the label.
3
4
Set the luminaire’s address throught the dip switch.
Dip switch
position
5
Luminaire assembly
>5mm