GENERAL
These luminaires are used indoors
(
ta
o
40 C
)
where emergency light is needed.
E a c h l u m i n a i r e m u s t b e c o n n e c t e d
permanently to the mains power supply.
ADDRESS OPERATION
The luminaires can be connected to a
GR-6500 address panel. For address
operations refer to the installation manual
o f t h e p a n e l . F o r a d d r e s s m o d u l e
connections see page
4
. For dip-switch
addressing selection see page
4
,
5
and
6
.
OPERATION DESCRIPTION
When the unit is connected to the main
power supply (after connecting the battery)
the indicator LAMP FAULT – BATT. FAULT
remains OFF whereas the indicator POWER
CHARGE blinks to indicate that the batteries
are charging. When the batteries are fully
charged this indicator will light permanently.
If this indicator does not light then probably
the battery has not been connected. If the
batteries are connected and the indicator
does not light then contact a qualified
service technician for assistance. The
charging procedure is monitored by a
microprocessor and is based on a 3 stage
cycle thus ensuring a fast and full charge of
the battery. The charge current is supplied by
a high efficiency switch mode power supply
which ensures perfect charging even during
the fluctuations of the mains power supply.
BATTERY CUTOFF
The unit enters this state during the power
supply failure and when the battery has been
fully discharged. In this state the luminaire
draws the least power from the battery in
order to prevent deep discharge.
MANUAL TESTING
Is accomplished by briefly (<1 sec.) pressing
the TEST button. This permits the user to
test the good operation of the luminaire’s
emergency circuit.
The unit simulates a
power failure and the lamps are lit using the
batteries. This manual test does not affect
the automatic test
.
Thank you for your trust in our products
Olympia Electronics - European manufacturer
Page
1
from
7
92303
7
00
8
_09_00
1
Aluminum, ABS/PC, PC
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Pb)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
<24h
POWER-CHARGE indicator, LAMP FAULT–BATT. FAULT indicator, TEST button
From overcharge and deep discharge
IP42
o
5 to 40 C
Up to 95%
3 years
(1
year for the battery
)
180 min
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
302 x 94 x 350 mm
220-240V AC/50-60Hz
12V/7Ah
16VA
4120gr.
3200lm
White Power LEDs
GRL-37/180/ADR
TECHNICAL CHARACTERISTICS
(
for LED MODULE Specifications see page
4
)
ADDRESSABLE SELF TESTING
NON MAINTAINED EMERGENCY LUMINAIRES
6310gr.
90 min
2x12V/7Ah
GRL-37/90/ADR