220-240V AC/50-60Hz
ABS/PC, PC
3 h
90 min
24 h
Charge, lamp fault, fault indication LED
, TEST button
From
overcharge and deep
discharge
IP65
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
o
5
to 40 C
Up to 95%
360 x 145 x 73 mm
915gr.
1005gr.
GR-938/4P
GR-938/6P
GR-939/6P
GR-939/4P
4.8V/1.5Ah
4.8V/3Ah
4.8V/4Ah(Ni-MH)
5.2W/5.5 VA
6.1W/6.4 VA
4.6W/5 VA
5.8W/6.2 VA
1060gr.
TECHNICAL CHARACTERISTICS
(
for LED MODULE Specs. see page 4)
4
white power LED’s
175lm / 350lm
245lm / 480lm
175lm / 350lm
245lm / 480lm
6
white power LED’s
6
white power LED’s
4
white power LED’s
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS
- CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (MAINS / EMERGENCY)
ILLUMINATION SOURCE
3 years (1 year for the battery)
GENERAL
These luminaires are used in places where
emergency luminaires are needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation the
led strip lights and the battery is charging. In
case of a mains power supply failure the
luminaire will light the led strip automatically
in emergency mode. When the mains power
supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
OPERATION
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost
its energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Battery charging
The battery charging is completely controlled.
In this case, is achieved the perfect battery
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance
current.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is
connected. By pressing the TEST/RESET
button briefly (page 3) an operation test is
initiated. During this test period all indication
LEDs are OFF.
Automatic test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
main power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the luminaire`s back up
operation. This test is conducted automatically
every six months. In order to be performed, the
main power supply and the battery should be
connected (the battery should be charged). If
the battery is not charged, the test is postponed
until the battery is completely charged. If the
luminaire’s duration is lower than the named
during the Automatic Autonomous Test, the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the technical characteristics. During
emergency mode, a LED strip test is also
performed.
Resetting Errors
Push the TEST/RESET button for 5 seconds, to
extinguish all the indicated LED errors (page 3).
Then the luminaire enters regular operation
WATERPROOF SELF TESTING ΜΑΙΝΤΑΙΝΕ
D
EMERGENCY LUMINAIRES
Page 1 from 4
923939008_09_01
7
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.