and  the  capacitors  should  be  connected  and 
fully  charged

If  the  capacitor  is  not  fully 

charged

the  test  is  postponed

 

until  the 

capacitor is  completely charged. 

Back Up Operation

The  capacitor’s  autonomous  duration    during 
emergency  mode  is  at  least  the  one  that  is 
stated in the list of the technical characteristics. 
During  emergency  mode,  a  LED  strip  test  is 
also performed.

Resetting Errors

Push the TEST/RESET button (page 3) for >10 
seconds, to delete all the indicated LED errors . 
Then    the  illumination  sign  enters  regular

 

operation mode.

Test switch

Pressing  the  test  switch  less  than  5  seconds 
will initiate a light source test (last for 3 secs). 
Pressing  the  test  switch  between  5  to  10 
seconds  will  initiate  a  manual  capacitor 
duration test. This test will not be  started if the 
capacitor  is  not  fully  charged  (i.e.  If  the  green 
LED is flashing). If the test switch is pressed for 

more than 10 seconds, the illumination sign will 
be reset (delete all errors).

ΑΤΤΕΝΤΙΟΝ!

!!

1.  Operations  for  installation,  maintainance  or 
testing  must  be  done  by  authorized  personel 
only

.

2.  The 

luminaire 

must  be  connected  to  the 

mains  power  supply  thru  a  fuse  dependent  by 
the total amount of the line’s  power load.
3.In  case  of  capacitors  or  lamp  replacement, 
these  must  be  replaced  by  parts  of  the  same 
type,  by  the  manufacturer  or  by  a  competent 
person.

4.  In  case  of  inactive  use  for  a  period  greater 
than  2  months,  disconnect  the  capacitor  by 
pulling out the connector when is fully charged.

 

5

I s not allowed to discard capacitors in to 

t i

common  trash  bins,  they  must  be 
d i s c a r d e d   o n l y  

 

i n   c a p a c i t o r ’s  

recycling points. Do not incinerate.

For wall or ceiling installation

Step 1. 

Remove the diffuser. Place a flat blade screwdriver and pull up gently the reflector.   

Step 2. 

Install the included plastic cover in to the unused hole and install the base plastic (with the 

included mounting screws and plugs).

  

 

Step 3. Always use in any case round mains cable

,

 with external diameter

 

of 

6-9

mm (H05RN-F 

type 2x1mm² 

or 

any 

other type

,

 

at least 

equal 

to it’s mechanical and electrical properties).   

ATTENTION!! The cable must not be deformed in any way (This requirement is important 
to ensure the tightness isolation IP 65). 

Install

 

the cable gland

,

 pass the round cable through

 

and tighten it all the way.

Step 4. 

Place the capacitor’s connector to the corresponding connector on the P.C.B

Step 5. 

Connect the mains cables to the respective terminal block 

(

connect the ground wire)

Ν

 

for 

neutral

L

 for live wire

 

and 

L1

 for the maintained operation

The 

L

1

 

wire can be connected

 

to an 

external switch to control the maintained or non maintained operation of the luminaire

For permanent 

maintained operation use two wires to power the luminaire, 

Ν

 

for neutral and 

L

 for live wire, and link 

the 

L

 and

 

L1

.

Step 6. 

Install the

 

included tie (if needed) to fasten securely the power cables.

Step 7. 

Refit the reflector and fasten the two small screws (included).

Step 8. 

Finally place the diffuser by using the 4 screws (tightening torque 1.2Nm)

 

Step 9. Manual TEST or Resetting Errors

In order to test or reset the device you must carefully remove the diffuser by unfastening the 4 
mounting screws. Then push the button as described in the according paragraphs on page 1 and 
2. 

NOTE!!
After finishing the installation you must power the luminaire at least for 3 hours for 
capacitor charging to perform the nominal autonomy.

Status of LEDs

Led status explanation

GREEN

YELLOW

RED

Normal

Charging

Capacitor’s duration test (auto or manual)

Capacitor’s fault

Capacitor’s fault and light source fault

Charger and capacitor’s fault (or mains off and capacitor fault)

Charger and light source fault (or mains off and light source fault)

Charger, capacitor and light source fault (or mains off, capacitor and light source fault)

Light source test

Light source fault

Continuous ON

Continuous OFF

Flashing at 1,2 Hz

Charger’s fault, capacitor not connected or mains off

LEDs

Description

L1 L N