INSTALLATION INSTRUCTIONS

For wall or ceiling installation
Step 1. 

Remove the diffuser. Place a flat blade screwdriver and pull up gently the reflector.   

Step 2. 

Install the included plastic cover in to the unused hole and install the base plastic (with the 

included mounting screws and plugs).

Step 3. Always use in any case round mains cable, with external diameter of 6-9mm (H05RN-F 
type 2x1mm² or any other type, at least equal to it’s mechanical and electrical properties).   
ATTENTION!! The cable must not be deformed in any way (This requirement is important 
to ensure the tightness isolation IP 65). 

Install

 

the cable gland, pass the round cable through 

and tighten it all the way.

Step 4. 

Place the capacitor’s connector to the corresponding connector on the P.C.B. 

Step  5. 

Connect  the  mains  cables  to  the  respective  terminal  block  (connect  the  ground  wire  if 

required). 

Ν

 for neutral, 

L

 for live wire and 

L1

 for the maintained operation. The 

L1

 wire can be 

connected  to  an  external  switch  to  control  the  maintained  or  non  maintained  operation  of  the 
luminaire. For permanent maintained operation use two wires to power the luminaire, 

Ν

 for neutral 

and 

L

 for live wire, and link the 

L

 and 

L1

.

Step 6. 

Install the included tie (if needed) to fasten securely the power cables.

Step 7. 

Refit the reflector and fasten the two small screws (included).

Step 8. 

Finally place the diffuser by using the 4 screws (tightening torque 1.2Nm). 

Step 9. Manual TEST or Resetting Errors

In order to test or reset the device you must carefully remove the diffuser by unfastening the 4 
mounting screws. Then push the button as described in the according paragraphs on page 1 and 
2. 

NOTE!!
After finishing the installation you must power the luminaire at least for 3 hours for 
capacitor charging to perform the nominal autonomy.

  

 

 

923900000_09_007