GENERAL

o

These  luminaires  are  used  indoors 

(

ta  40 C

)

 

where emergency light is needed. Each luminaire 
must be permanently connected to mains power 
supply

.

  In  normal  operation  (L1  connected  to  L) 

the led strip lights and the battery is charging. In 
case  of  a  mains  power    supply  failure    the   
luminaire   will   light the led strip automatically in 
emergency mode (powered by its battery). When 
the  mains    power  supply  is  restored  the  device 
turns to normal operation. 

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 

2

.

OPERATION
Battery Charging

The battery charging is completely controlled

In 

this case, the best possible   battery maintenance 
is

 

achieved

as  well  as  the  elongation  of  its 

duration

When  the  battery  has  completely 

charged

it charges with a maintenance current.

Battery Cut-off

The  luminaire  enters  in  this  operation  when  the 
mains power supply fails

 

and battery has lost its 

energy

During this operation the luminaire enters 

the idle state

 

and 

battery  consumption  is  negligible,  in  order  to  be 
protected from deep discharge.

Manual

 

 

Test

The manual test can be conducted only if the main 

power  supply  and  the  battery  is  connected.  By 
pressing the test button briefly an operation test is 
initiated. During this test period all indication LEDs 
are OFF.

Automatic Operational Test

This test includes all the operations that provide 
the  manual  test  and  is  conducted  automatically 
every 15 days. In order to be performed, the main 
power  supply  and  the  battery  should  be 
connected. 

Automatic Autonomous Test

The Automatic Autonomous Test is conducted and 
measures the luminaire`s back up operation. This 
test is conducted automatically every six months

In order to be performed, the main power supply 
and the battery should be connected (the battery 
should be charged)

If the battery is not charged

the  test  is  postponed

 

until  the  battery  is   

completely  charged.  If  during  the  Automatic 
Autonomous Test the luminaire’s duration is lower 
than  the  nominal,  then  the  battery  must  be 
replaced.

Back Up Operation

The  autonomous  duration  of  battery  during 
emergency mode is at least the one that is stated 
in the technical characteristics. During emergency 
mode, a LED strip test is also performed.

Resetting Errors

Push the Test button for 

10

 seconds, to delete all 

the  indicated  LED  errors.    Then  the  luminaire 
enters regular

 

operation mode.

Page

 

1 from

 

3

923416001_09_00

8

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

                         3D LIGHT SELF TESTING MAINTAINED EMERGENCY LUMINAIRES 

220-240V AC/50-60Hz

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES

 (

Ni-Cd

)

CHARGING TIME

INDICATIONS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION SOURCE 

90min

24h

Charge, Lamp Fault, Battery Fault indication LED

TEST Button

From overcharge and deep discharge

IP40

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

, EN 1838

5 to 40  C

o

Up to 95% 

3 years 

(1 

year for the battery

)

180min

4.8V/3Ah

4.8V/1.5Ah

  460lm / 460lm 

  4 power LEDs 

3

20

 

x 310 x 310 mm

ABS/PC, PC

2900gr.

2820gr.

11VA

GR-416/4P

GR-415/4P

14VA

ILLUMINATION

 

(230V AC

 

/ emergency) 

TECHNICAL CHARACTERISTICS

 

(for LED MODULE Specs. see page 3)

 

CONTROLS