GENERAL
o
These luminaires are used indoors
(
ta 40 C
)
where emergency light is needed. Each luminaire
must be permanently connected to mains power
supply
.
In normal operation (L1 connected to L)
the led strip lights and the battery is charging. In
case of a mains power supply failure the
luminaire will light the led strip automatically in
emergency mode (powered by its battery). When
the mains power supply is restored the device
turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page
2
.
OPERATION
Battery Charging
The battery charging is completely controlled
.
In
this case, the best possible battery maintenance
is
achieved
,
as well as the elongation of its
duration
.
When the battery has completely
charged
,
it charges with a maintenance current.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails
and battery has lost its
energy
.
During this operation the luminaire enters
the idle state
and
battery consumption is negligible, in order to be
protected from deep discharge.
Manual
Test
The manual test can be conducted only if the main
power supply and the battery is connected. By
pressing the test button briefly an operation test is
initiated. During this test period all indication LEDs
are OFF.
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the main
power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted and
measures the luminaire`s back up operation. This
test is conducted automatically every six months
.
In order to be performed, the main power supply
and the battery should be connected (the battery
should be charged)
.
If the battery is not charged
,
the test is postponed
until the battery is
completely charged. If during the Automatic
Autonomous Test the luminaire’s duration is lower
than the nominal, then the battery must be
replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the technical characteristics. During emergency
mode, a LED strip test is also performed.
Resetting Errors
Push the Test button for
10
seconds, to delete all
the indicated LED errors. Then the luminaire
enters regular
operation mode.
Page
1 from
3
923416001_09_00
8
Thank you for your trust in our products
Olympia Electronics - European manufacturer
3D LIGHT SELF TESTING MAINTAINED EMERGENCY LUMINAIRES
220-240V AC/50-60Hz
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES
(
Ni-Cd
)
CHARGING TIME
INDICATIONS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION SOURCE
90min
24h
Charge, Lamp Fault, Battery Fault indication LED
,
TEST Button
From overcharge and deep discharge
IP40
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
, EN 1838
5 to 40 C
o
Up to 95%
3 years
(1
year for the battery
)
180min
4.8V/3Ah
4.8V/1.5Ah
460lm / 460lm
4 power LEDs
3
20
x 310 x 310 mm
ABS/PC, PC
2900gr.
2820gr.
11VA
GR-416/4P
GR-415/4P
14VA
ILLUMINATION
(230V AC
/ emergency)
TECHNICAL CHARACTERISTICS
(for LED MODULE Specs. see page 3)
-
CONTROLS