olympia electronics GR-2100 Скачать руководство пользователя страница 1

923211010_09_001

Page 1 from 5

SELF TESTING MAINTAINED EMERGENCY LUMINARY WITH WIRELESS COMMUNICATION

Battery Charging

The battery charging procedure is controlled by 
the processor, thus maintaining its best possible 
preservation, as it extends its duration.

GENERAL

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

The luminaire enters this mode when the mains 
power  supply  fails  and  battery  has  lost  all  its 
energy.  During  this  operation  the  luminaire 
enters the idle state and battery consumption is 
negligible,  in  order  to  be  protected  from  deep 
discharge.

Battery Cut-off

o

These  luminaires  are  used  indoors  (ta  40 C) 
where emergency light is needed.
Each luminaire must be permanently connected 
to mains power supply. In normal operation the 
illumination  LEDs  are  lit  as  well  as  the  green 
indicating  charge  LEDs  when  the  battery  is 
charging.  In  case  of  a  mains  power  supply 
failure,  the  luminaire    enters  in  emergency 
mode  and  will  light  automatically.  When  the 
mains power supply is restored the device turns 
to normal operation.

This test can be done by pressing the test 

Manual Operational Test

Automatic Operational Test

This  test  includes  all  the  operations  of  the 
manual  test  and  is  conducted  automatically 
every  15  days.  In  order  to  be  performed,  the 
mains  power  supply  and  the  battery  should  be 
connected. 

Automatic Autonomy Test

The  Automatic  Autonomy  Test  measures  the 
device’s  back  up  operation  and  emergency 
duration.  This  test  is  conducted  automatically 
every  6  months.  In  order  to  be  performed,  the 
mains  power  supply  and  the  battery  should  be 
connected and fully charged. If the battery is not 
fully  charged,  the  test  is  postponed  until  the 
battery is completely charged. If during this test, 
the  autonomy  is  less  than  nominal,  the  battery 
fault  led  turns  on  continuously  and  the  battery 
must be replaced. 

button.  The  light  source  and  the  emergency 
circuit of the device are monitored for 3 sec. The 
manual test can be conducted only if the mains 
power  supply  and  the  battery  are  connected. 
During  this  test  period  all  indication  LEDs  are 
OFF. 

Olympia Electronics - European manufacturer

Thank you for your trust in our products  

220-240V AC/50-60Hz

3.6V/1.5Ah

3.6V/600mAh

3.3W / 3.6VA

TECHNICAL CHARACTERISTICS

 (

for LED MODULE Specs. see page 2)

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY  (Ni-Cd)

GR-2100/ST/M/WL

GR-2110/ST/M/WL

3 h

1.5 h

24 h

16 h

IP30

o

5 to 40  C

up to  95% 

ABS/PC,PC

557gr.

476gr.

292 x 111 x 54 mm

  100lm / 100lm

22m

  12 White LEDs

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT
GUARANTEE 

CHARGING TIME

INDICATIONS - CONTROLS

MINIMUM AUTONOMY DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

ILLUMINATION 

(230V AC / emergency) 

VEWING DISTANCE

ILLUMINATION SOURCE 

Battery and charge Fault indication LEDs, TEST button

3 years (1 year for the battery)

Tx power

Tx/Rx frequency range

11dBm

868 - 870MHz

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2,

ΕΝ 61000-3-3, ETSI EN 303 446-1 v1.1.0, ETSI EN 300 220-2 v3.1.1