Page
2
from
4
supply and the battery should be connected
and fully charged
.
If the battery is not fully
charged
,
the test is postponed
until the battery
is completely charged. If during this test, the
autonomy is less than nominal then the battery
fault led turned on continuously and the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated
in
the
list
of
the
technical
characteristics. During emergency mode, a
light source test is also performed.
Resetting Errors
Place the test card A-1900 on the side of the
indications (page 4) and remove it after the
reset is conducted (the indications light in
sequence), to delete all the indicated LED
errors. Then the luminaire enters regular
operation mode.
Indication LED status (with connected
mains power supply).
Charge
On:
Good charge condition.
Οff:
No battery
(
No charging current
or disconnected battery
).
Lamp Fault
with L1 connected to L
Οn
(with LED strip off)
:
Faulty LED strip
(must be replaced).
Οn
(with LED strip on)
:
Problem in the back
up circuit of the LED strip (must be checked by
an authorized personnel).
Off:
Good LED strip.
Battery Fault
Ο
ff
:
Battery OK.
Blink
(
With Charge LED ON):
Autonomy or
low battery problem
(the battery must be
replaced).
Blink
(
With Charge LED Off):
No charging
current or disconnected battery
.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only
.
2.
The device must be connected to the mains
power supply through a fuse dependent on the
total amount of the line’s power load
.
In case of battery or lamp replacement,
these must be replaced by parts of the same
type, by the manufacturer or by a competent
person.
3.
4. In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery’s connector.
5
.
I s not allowed to discard batteries in to
common trash bins, they must be
discarded only
t i
in battery recycling
points. Do not incinerate.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
1:
Maintained (*)
A:
Including test device
G:
Internally illuminated
*90:
1.5 hour duration
180:
3 hours duration
(*)
Maintained operation: The luminaire lights
its illumination source, when it is powered by
the mains power supply or not
.
Non Maintained operation: The luminaire lights
its illumination source,
only in power supply’s
failure.
Note!! T
he installer should fill in
, on the
specification label,
the letter
G
if the luminaire is
used as a safety sign
.
NOTE!! After finishing the installation you
must power the luminaire at least for 24
hours for battery charging to perform the
nominal autonomy.
Battery replacement
It can be done only by a competent person
and after the mains interruption
.
1. Follow the step 1 of the installation
insrtuctions and remove the diffusor.
2. Remove the reflector (step 1 of the
installation instructions).
3. Remove the old battery and place a new on
of the same type and characteristics.
4. Replace the removed parts (previous steps
1, 2).
The light source contained in this luminaire
s h a l l o n l y b e r e p l a c e d b y t h e
manufacturer, or his agent, or a similar
qualified person.
N O T E ! T h e l i g h t s o u r c e i s n o n - u s e r
replaceable.
923193901_09_008
X
1
8
1
0
A
G