DESCRIPTION  

The  Addressable Fire Alarm systems BSR-100x of 
1,2 and 4 loop outputs, all sharing the same 
control interface, functionality and indications. 
The provided software PC-1004 for Windows PC, 
not only provides utilities and tools for 
calculating installation parameters, but also is 
able to set and configure the control panel as 
well as keeping an event log record. All the 
models include 4 outputs for conventional 
sirens, three BMS relays and 24V outputs. 
 Each loop output connection can support 
up to 150 addressable units and the “ Loop 
Calculator ” tool shall be used for cable selection 
according to your installation size. All features 
and indications are in accordance with European 
standards ΕΝ 54 - 2 and ΕΝ 54 - 4.  

 

PRODUCTS 
-

 BSR-1001 – 1 LOOP 

-

 BSR-1002 – 2LOOP 

-

 BSR-1004 – 4LOOP 

 

SPECIFICATIONS

 

Dimensions: 355 x 115 x 345mm 
Weight : <4.33Kg (Without batteries) 
Input Power: 230VAC, 50-60Hz, <130VA 
Operating Temperature: -5° ~40°C (23°F – 104°F) 
Degrees of cover protection : IP30 

 

CAUTION 

This product may only be installed or 

maintained by a qualified Electrician. 

The system must be installed in accordance 

with national regulations and requirements. 

-

 All power must be disconnected before 

installation or maintenance. 

Only original spare parts must be used for this 

product. 

The panel is compatible only with the 

corresponding Olympia Electronics addressable 
luminaires. 

NEEDED MATERIALS 

Mounting Hardware. 

Screwdrivers 

Multi-meter 

Pliers

 

Cutter 

 

MAINTENANCE

 

The periodical checks must follow the EN54-14 
or be verified according to local regulations. 

WARRANTY 

Olympia Electronics guarantees the quality, 
condition and operation of the goods. The 
period of warranty is specified in the official 
catalogue of Olympia Electronics and also in the 
technical leaflet, which accompanies each 
product. This warranty ceases to exist if the 
buyer does not follow the technical instructions 
included in official documents given by Olympia 
Electronics or if the buyer modifies the goods 
provided or has any repairs or re-setting done by 
a third party, unless Olympia Electronics has fully 
agreed to them in writing. Products that have 
been damaged can be returned to 
the premises of our company for repair or 
replacement, as long as the warranty period is 
valid. Olympia Electronics reserves the right to 
repair or to replace the returned goods and to or 
not charge the buyer depending on the reason 
of defection. Olympia Electronics reserves the 
right to charge or not the buyer the 
transportation cost. 
 

 

CONTACT  DETAILS 

72nd km. O.N.R. Thessaloniki-Katerini 
P.C. 60300 P.O. Box 06 Εginio Pierias Greece 

www.olympia-electronics.gr 

[email protected]

 

Tel. +30 23530 51200 

 

 

 

Содержание BSR-100 Series

Страница 1: ...1 921100400_90_001_QG_EN Addressable Fire Detection System BSR 100X Quick Installation Guide Generic Design FIRE...

Страница 2: ...nal spare parts must be used for this product The panel is compatible only with the corresponding Olympia Electronics addressable luminaires NEEDED MATERIALS Mounting Hardware Screwdrivers Multi meter...

Страница 3: ...by the number of each type and find the total consumption of all points The total consumption should not exceed the 400mA per Loop in alarm state Having the estimated cable distance cable cross sectio...

Страница 4: ...nection We recommend FIP200 MICC PYROFIL Choose the correct cross section for each zone Refer to the previous table All points must be connected according to the following diagrams Fig 1 Mounting hole...

Страница 5: ...5 921100400_90_001_QG_EN Fig 3 General connection diagram...

Страница 6: ...6 921100400_90_001_QG_EN Fig 4 Loop Diagram Fig 5 Detector base connections BSR 6155 BSR 6157 and BSR 6160 Optional BSR 5072 Remote LED...

Страница 7: ...7 921100400_90_001_QG_EN Fig 6 Connection of manual call point BSR 5136 Fig 7 Addressable Siren connection...

Страница 8: ...8 921100400_90_001_QG_EN Fig 8 Input Output unit BSR 8120 connection Fig 9 Conventional Siren connection Fig 10 Panel Network connections...

Страница 9: ...9 921100400_90_001_QG_EN Fig 11 Extra Relay BS 613 placement Optional On Demand Fig 12 External modules placement Note Place the Ethernet Adaptor all the way to the left i e use the first 10 pins...

Страница 10: ...ply has been applied to any BSR 8120 device of an installation before you perform AUTOADDRESSING or POINT DETECTION see page 11 After these actions are complete then apply again the 24V external power...

Страница 11: ...S TECHNICIAN MENU SETUP Configure and setup the AUX RELAY TECHNICIAN MENU SETUP Configure and setup the EXTRA RELAYS Optional TECHNICIAN MENU PANEL NETWORK Select PANEL ADDRESS Set Panel address 1 if...

Страница 12: ...to be replaced Wrong type or operating voltage batteries The charger cuts off and restarts the system Protection circuit is enabled Replace the batteries 2x12V 7Ah 9Ah 12Ah or 15Ah TECHNICIAN MENU SE...

Страница 13: ...Make sure the EARTH conductor and cable shield have infinite Ohms across the L L LF and LF 2 If the USB cable is connected with a PC it is normal OPEN CIRCUIT 1 Point not connected 2 Incorrect wiring...