optically visible LED.

In every device there is a double sticker with the UID (Unique Identifier) number. This 
number is unique for each device.

UID: 

These functions combined with periodic manual testing ensure maximum security level. The 
manual testing procedure is carried out by spraying a small amount of smoke into the detector 
with an A-752 spray or a counterpart product. It is suggested to carry out a test every 6 months 
or after a change in the position of the sensor. A key element of its proper function is the air to 
be able to freely circulate inside it. So be careful not to block the openings of the outer cover. 
Before the manual testing it is suggested to enable the special “walk in test” mode from the 
panel.

CAUTION !!

After installation the device must not be covered with dust or be painted or anything else 
happen that will block the smoke to get to the sensor. Special attention must be given during 
the installation and the use of the device, since the user assumes full responsibility for proper 
operation afterwards.
Also, during site works place the plastic cover to the detector as shown in the picture below to 
protect the device from dust.

- Automatic fault diagnosis.

- Dust compensation and automatic indication when cleaning is required. Stable 

level of detection regardless of detector’s working hours.

- Integration of dynamic algorithms for noise and false alarm rejection.

Additional features of the device :

- Compensation of smoke measurements based on ambient temperature which 

ensures high precision measurements even under extreme environmental 
conditions. 

Page 2 from 4

921655004_09_005

5.

       

Connected to the cable’s shield (when shield is used).

2. -  IN : 

It is connected to the zone of the panel or to the (

- OUT

) contact of the 

previous detector.

4. -  R :

 It is connected with BS-572.

1. + IN/OUT :

 It is connected to the zone of the panel or to the (

+ IN/OUT

contact of the previous detector.

CONNECTION

3. -  OUT :

 It is connected to the next detector (

- IN

) or if it is the last one to the terminal 

resistor.

1. Remove the detector from its base rotating to the left till the side marks are aligned.
2. Fasten the base with the supplied mounting materials (point 5).
3. Connect the power cables (minding the correct polarity) according to the requirements of 

the installation (Figure 1, 2).

4. Place the detector carefully so that the side marks are on the same position and rotate the 

detector clockwise until it locks. Power the device and after 3-5 seconds it is ready for 
operation.

Installation process

Installation process

-R

U

T

/O

N

  I

+

N

  -

   

I

T

U

-  

   

O

-R

U

T

/O

N

  I

+

N

  -

   

I

T

U

-  

   

O

Connection

If the power of the detectors is turned off, wait for 3-5 seconds before you turn the power on 
again. 

Term

inati

ng

resis

tor

Figure 2

Fr om z one

of the pa ne l

Mounting base

Figure 1

2

Connection
with exterrnal
LED 

Page 3 from 4