They are composed by two parts. A plastic base which is placed on the ceiling and the main
body of the detector which fits on the plastic base with a simple rotation to the right. The
o
detectors have a 360 visible led and a remote led driver which are light up constantly in case
of detection of fire, till cancelled from the panel. They are turned off only when a reset
command is given from the panel. The indicator led blinks every 6 sec indicating the normal
function.
The detector has fault diagnosis and dust compensation functions, which automatically
informs you through the onboard LED when replacement or cleaning actions are required.
The indication LED blinks every 7 seconds. In normal operation it blinks 1 time, if cleaning
action is required it blinks 2 times and if there is a failure it blinks 3 times. After cleaning
procedure it will take about 10 minutes for detector’s working indication to return to normal.
GENERAL
The user have to read carefully the following instructions, in order to be properly informed and
keep them for future use.
The BS-655/A is a conventional smoke detector which integrates function of optical smoke
detection. The detector transitions to alarm state when the concentration of smoke reaches
0.107dB/m.
INSTALLATION
The detectors should be placed in the ceiling in visible points without side obstacles, away
from places that are barely ventilated or with strong air currents and water vapor. Each
2
detector covers an area of 50 m while the distance between two detectors should not be
more than 15m. Also, they must be placed at least 50 cm away from fluorescent lamps. Cable
diameter should be from
. to .
0 5
2 5mm
.
MAINTENANCE & FUNCTIONAL TESTING
90μΑ
17-30V DC
IP42
EN 54-7
12mA (with activated onboard LED)
0.107 dB/m
ABS/PC
158 gr.
103 (d) x 48 (h) mm
1mΑ for 2 sec
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
START UP POWER CONSUMPTION
OPERATION VOLTAGE
Thank you for your trust in our products
Olympia Electronics - European manufacturer
INDICATORS
OUTPUT
SMOKE CONCENTRATION SENSITIVITY
STANDBY CONSUMPTION
ALARM CONSUMPTION
TECHNICAL CHARACTERISTICS
Up to 95%
ο
-40 to 70 C
To panel / to external LED driver (BS-572)
Alarm LED
2 years
Page 1 from 4
BS- 655/A
Optical smoke detector
921655004_09_005
Warranty
Warranty
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
[email protected]
Olympia Electronics guarantees the quality, condition and operation of the goods. The period
of warranty is specified in the official catalogue of Olympia Electronics and also in the
technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer
does not follow the technical instructions included in official documents given by Olympia
Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done
by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that
have been damaged can be returned to the premises of our company for repair or
replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not
charge the buyer depending on the reason of defection. Olympia Electronics reserves the
right to charge or not the buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
Page 4 from 4
921655004_09_005
1293
21
EN 54-7:2018
DoP: 921655004_59_001
EGINIO
PIERIAS
60300
GREECE
BS-655/A
Optical smoke detector