HORIZONTAL VENT INSTALLATION:

HORIZONTAL VENT INSTALLATION:

HORIZONTAL VENT INSTALLATION:

HORIZONTAL VENT INSTALLATION:

HORIZONTAL VENT INSTALLATION:

A.  The boilers covered in this section are design-certified as CATEGORY 3 for venting,

only when they are installed with manufacturer specified vent system components and
installation practices.

B.  Install vent pipe beginning at the vent connector and work toward the vent cap.
C. Vent pipe and fittings MUST NOT be routed into, through, or within any other vent,

such as an existing masonry chimney or factory built chimney. (Recommended installation
is shown in figure 1 page 3, unacceptable installation is shown in figure 2 page 3).

D. Vent pipe lengths. The maximum length is the combined length of straight horizontal

and vertical runs, and the equivalent straight length of fittings. The required lengths for each
boiler are as follows:

VENT PIPE LENGTHS

Vent Pipe

VENT LENGTHS

EQUIV.

Model

Dia.

Maximum

Minimum

feet per fitting

ODV50/100

3"

30' W/

Condensate

2' W/1

5'

Tee & 2 Elbows

Elbow

ODV125

3"

25' W/1

2' W/1

5'

Elbow

Elbow

ODV150/200

4"

30' W/1

2' W/1

5'

Elbow

Elbow

Example: 20 feet of vent pipe w/1 elbow is Equivalent to 15 feet of vent pipe w/2
elbows. Note, condensate trap is not required on models ODV150 thru 200.

E.  The vent pipe should slope upward  from the boiler at least 1 inch for every 4 feet.

F.  No portion of the vent pipe should have dips or sags where condensate could collect,

see figure 3 on page 3 for a typical vent system.

G. Rigidly support vent pipe every 5 feet and at the elbows. Plumbers straps may be

used.

H. Clearances and enclosures. ALL vent pipe and fittings must be installed with

appropriate air space clearances to combustibles. These air space clearances apply to

indoor  or outdoor vents, whether they are open, enclosed, horizontal or vertical or pass

through floors, walls, roofs, or framed spaces. The appropriate air space clearances should

be observed to joists, studs, subfloors, plywood, drywall, or plaster enclosures, insulated

sheathing, rafters, roofing, and any other combustible material. The minimum air space

clearance also applies to electrical wires and any kind of building insulation.

WARNING:

WARNING:

WARNING:

WARNING:

WARNING:

DO NOT INSULATE OR OTHERWISE WRAP VENT PIPE OR

FITTINGS.

For Horizontal runs 

For Horizontal runs 

For Horizontal runs 

For Horizontal runs 

For Horizontal runs 

maintain a minimum air space clearance of 6 inches for 3 inch and

4 inch vent pipe to any combustible material, electric wires, and building materials.

Содержание ODV-B

Страница 1: ...V V V V B B B B B GAS FIRED BOILERS FOR FORCED HOT WATER ECR International Ltd Olsen Division P O Box 900 Wallaceburg Ont N8A5E5 VENTING ADDENDUM VENTING ADDENDUM VENTING ADDENDUM VENTING ADDENDUM VE...

Страница 2: ...NSTALLATION PAGE 4 FLEX L PIPING COMPONENTS PAGE 5 HEAT FAB PIPING COMPONENTS PAGE 6 Z FLEX PIPING COMPONENTS PAGE 7 PROTECH PIPING COMPONENTS PAGE 8 CONDENSATE DRAINS PAGE 9 LOCATING THE VENT TERMINA...

Страница 3: ...F BOILERS AND ALL INSTALLATIONS OF BOILERS AND ALL INSTALLATIONS OF BOILERS AND ALL INSTALLATIONS OF BOILERS AND ALL INSTALLATIONS OF BOILERS AND VENTING SHOULD BE DONE ONLY BY A QUALIFIED EXPERT AND...

Страница 4: ...ivalent to 15 feet of vent pipe w 2 elbows Note condensate trap is not required on models ODV150 thru 200 E The vent pipe should slope upward from the boiler at least 1 inch for every 4 feet F No port...

Страница 5: ...PAGE 3 FIGURE1b FIGURE 2 FIGURE 3 FIGURE1a...

Страница 6: ...PICAL INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION Notes 1 A condensate tee drain is only needed when horizontal vent lengths exceed 10 feet 2 Insert vent pipe in boiler venter outlet vent ada...

Страница 7: ...nts Notes 1 A condensate tee drain is only needed when horizontal vent lengths exceed 10 feet 2 Insert vent pipe in boiler venter outlet vent adapter apply silicone completely around edge of outlet an...

Страница 8: ...onents PAGE 6 FIGURE 6 Notes 1 A condensate tee drain is only needed when horizontal vent lengths exceed 10 feet 2 Insert vent pipe in boiler venter outlet vent adapter apply silicone completely aroun...

Страница 9: ...ent Pipe Components Notes 1 A condensate tee drain is only needed when horizontal vent lengths exceed 10 feet 2 Insert vent pipe in boiler venter outlet vent adapter apply silicone completely around e...

Страница 10: ...Vent Pipe Components Notes 1 A condensate tee drain is only needed when horizontal vent lengths exceed 10 feet 2 Insert vent pipe in boiler venter outlet vent adapter apply silicone completely around...

Страница 11: ...ersinstructions J See the latest revision of the NFGC ANSI Z223 1 When installed in Canada The latest revision of the CAN CSA B149 Natural Gas and Propane Installtion Code FIGURE 9 CONDENSATE DRAINS C...

Страница 12: ...PAGE 10 FIGURE10 NOTE IF THERE IS A POTENTIAL FOR EXCESSIVE WINDS SPECIAL CONSIDERATION SHOULD BE GIVEN TO LOCATE THE VENT TERMINATION AWAY FROM THE WINDWARD SIDE OF THE BUILDING...

Страница 13: ...nting CATEGORY 1 Appliances have non positive vent static pressure and rely on the heat content of combustion products to vent You may common vent CATEGORY 1 boilers The boilers covered by this manual...

Страница 14: ...e by locating boiler as close as practical to vent or chimney Avoid unnecessary turns or bends which create resistance to flow of vent gases Adding an elbow adds resistance For example adding a 6 90 d...

Страница 15: ...1 clearance on all sides to reduce the possibility of condensate in vent Condensate may cause vent to deteriorate allowing combustion products to collect in structure which could result in injury or...

Страница 16: ...t pipe must extend at least three feet above the point where it passes through the roof Vent termination must be at least two feet higher than any portion of building within ten feet horizontal andven...

Страница 17: ...r foot To prevent sagging at each joint support vent connectors and horizontal portions using hangers straps or equivalent Seal all connections where vent connectors enter chimney See Figure 11 on pag...

Страница 18: ...e National Fuel Gas Code ANSI Z223 1 NFPA54 In Canada CAN CSA B149 PAGE 16 FIGURE16 VER VER VER VER VERTICAL TICAL TICAL TICAL TICAL VENTING INST VENTING INST VENTING INST VENTING INST VENTING INSTALL...

Страница 19: ...DRAFT TURAL DRAFT TURAL DRAFT TURAL DRAFT TURAL DRAFT W W W W WA A A A ATER HEA TER HEA TER HEA TER HEA TER HEATER 40 000 BTU HR TER 40 000 BTU HR TER 40 000 BTU HR TER 40 000 BTU HR TER 40 000 BTU HR...

Страница 20: ...37616301 PAGE 18 REV 5 1 March 2004 FIGURE18...

Отзывы: