8

Activating the combustion air damper

Display

Action

Description

menu select

settings

information

operation mode

or

            

The combustion air damper must be activated in the 

service level.

Go to the service level via the menu selection, “in-

formation”.

information

service

op.hours

Ver.

ext.req.

GSM mod.

error messages

operating data

service level

on

n.c.

1.00.35  L6

2000h

0h

or

            

Service level

next

code

enter

0000

or

            

The password for the service level is: 2012

service level

input data

parameter

relay

components

service

or

            

Go  to  the  “components”  menu  using  ↓  or  ↑  and 

(ENTER).

components

grate

supply air

convection

no

no

no

or

            

Select “no” with (ENTER) (“no” flashes) and with

 

↓ or ↑ change over to “yes”.
Confirm “yes” with (ENTER).

The combustion air damper is now activated.

Содержание 43/1481.9240

Страница 1: ...Verbrennungsluftklappe 43 1481 9240 Combustion air damper Clapet d air de combustion Anleitung Seite 2 5 Instruction Page 6 9 Instructions Page 10 13 D GB F...

Страница 2: ...llen anderen Betriebszust nden Bereit Z nden Start ist sie ge ffnet Achtung Zum Erreichen der Endposition Zu ben tigt der Stellmotor ca 2 Minuten d h wenn die Anzeige Aus am Display erscheint darf das...

Страница 3: ...ckwand bzw in der Ger teanleitung b Stecker S5 auf Position S5 der Hauptplatine aufstecken c Stecker L Dauer auf Stecker L Dauer des Ger te Kabelbaums aufstecken Stutzen der Verbrennungsluftklappe in...

Страница 4: ...l St rmeldungen Betriebsdaten Serviceebene ein n v 1 00 35 L6 2000h 0h oder Serviceebene Weiter eingeben Kennwort 0000 oder Das Kennwort f r die Serviceebene lautet 2012 Serviceebene Info Eing nge Par...

Страница 5: ...ion gepr ft werden Dazu die Verbrennungsluftklappe im Men Relaistest ein und ausschalten Mit oder und mit ENTER in das Men Relaistest wechseln Relaistest Schnecke Saugzug Z ndung Rost Pumpe Zuluftklap...

Страница 6: ...open in all other operation modes standby ignition start Important It takes the servo motor approx 2 minutes to reach the end position Closed i e when the display reads off you must wait for at least...

Страница 7: ...pellet stove b Connect plug S5 onto position S5 of the main circuit board c Connect plug L Dauer L continuous onto plug L Dauer L continuous of the appliance s wir ing harness Insert the duct of the c...

Страница 8: ...urs Ver ext req GSM mod error messages operating data service level on n c 1 00 35 L6 2000h 0h or Service level next code enter 0000 or The password for the service level is 2012 service level input d...

Страница 9: ...do this switch the combustion air damper on and off in the relay test menu Go to the relay test menu using or and ENTER relay test auger exhaust ignition grate pump supply air convection off off off...

Страница 10: ...de service standby allumer d part il est ouvert Attention Il faut environ 2 minutes au moteur de com mande pour atteindre la position finale fer m c est dire que lorsque l annonce off s affiche l cra...

Страница 11: ...u dans le ma nuel d instruction de l appareil b Enficher le connecteur S5 en position S5 de la carte syst me c Enficher le connecteur L Dauer L Dur e sur le connecteur L Dauer L Dur e du fais ceau de...

Страница 12: ...therm ext mod GSM info d erreurs information menu SAV on n i 1 00 35 L6 2000h 0h ou menu SAV suiv code entrer 0000 ou Le mot de passe pour le menu SAV est 2012 menu SAV info param tres test sortie ac...

Страница 13: ...ur ceci allumer et teindre le clapet d air de combustion dans le menu test sor tie Passer au menu test sortie avec ou et avec ENTER test sortie vis sans fin extracteur allumage grille pompe air combus...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...1 78 4643 1486 07 2015 Olsberg GmbH H ttenstra e 38 59939 Olsberg T 49 2962 805 0 F 49 2962 805 180 info olsberg com olsberg com...

Отзывы: