4.

 

COOLING MODE 

 

 

 Selectable only with the remote control. The fan is always powered working at the speed selected even if the 

compressor is powered (except for the possible triggering of the anti-explosion sub programme), otherwise it 

works  at  minimum  speed.  If  automatic  fan  speed  is  selected  (on  the  remote  control)  the  following  is 

applicable (only with the compressor ON – if the compressor is OFF speed will always be minimum):  

i.

 

- if Tamb<T_set+3°C minimum fan speed is activated; 

ii.

 

- if T_set+3<Tamb<T_set+6°C medium fan speed is activated; 

iii.

 

- if Tamb>T_set+6°C maximum fan speed is activated. 

 

Between one automatic speed change and another at least 3 minutes must elapse. 

 

 The  compressor  is  turned  on  for  Tamb>=Tset+Hy  and  turned  off  for  Tamb<=Tset  (except  if  the  anti-ice 

programme  turns  on).  The  antiexplosion  sub  programme  forces  the  fan  to  work  at  top  speed  (only  if  the 

compressor is working) for ambient temperature Tamb>Tmax; the sub programme finishes for TambîTmax-

2°C  (without  any  time  limits).  The  anti-ice  sub  programme,  that  starts  at  Tamb<Tmin  and  finishes  at 

Tamb>Tmin+2°C, cyclically interrupts the compressor with Tp_on and Tp_off timings. 

 

 The set-point (Tset) can be adjusted on the remote from 18°C to 30°C with 1°C steps; minimum scale value 

(Scala_m),  hysteresis  (Hy)  and  scale  point  steps  (Step)  can  be  set  during  programming.  Activation  of  the 

compressor  must  be  after  a  minimum  Rest_time  (180sec)  after  powering  of  the  circuit  or  after  a  previous 

compressor switch-off. All the malfunctions that are expected for the machine are enabled in this status.  

 

 

 

 

 

5.

 

DEHUMIDIFIER MODE 

 

 

  Selectable  only  with  the  remote  control.  It  works  very  much  like  cooling  except  for  fan  speed  selection 

which is forced at minimum (and cannot be changed), the Tset setting which is set equal to Tamb each time 

the function is activated (and then cannot be changed) and for compressor operation which is controlled in the 

following way: 

i.

 

- ON continuously for Tamb>Tset+2°C 

ii.

 

- 6 minutes ON and 6 minutes OFF for Tset-2°C<Tamb<Tset+2°C 

iii.

 

- 6 minutes ON and 12 minutes OFF for Tset-4°C<Tamb<Tset-2°C 

iv.

 

- OFF continuously for Tamb<Tset-4°C 

 

In this condition, the antiexplosion and anti-ice sub programmes are enabled and all the malfunctions that are 

expected for the machine can be signalled. 

 
 
 

6.

 

NIGHTTIME MODE  

 

 

 Selectable  only  with  the  remote  control.  This  mode  can  only  work  with  the  cooling  function.  When  the 

NIGHTTIME mode is activated, fan speed is forced at minimum and the Tset is increased 1°C after 1 hour 

and  then  again  1°C  after  2  hours.  Changing  the  Tset  on  the  remote,  putting  the  machine  in  Standby  or 

powering off resets the function’s timer. All the malfunctions that are expected for the machine are enabled in 

this status. 

Содержание ISSIMO 11

Страница 1: ...remote control range distance angle m 8 80 Dimensions Width x Height x Depth mm 520x485x550 Weight without packaging Kg 36 Noise sound power db A min max 34 43 Enclosure protection rating IP20 Refrigerant load Type Kg R410A Max operating pressure MPa 5 2 Power lead No poles x sect mm2 3 x 1 5 Fuse 10AT Indoor temperature Outdoor temperature Maximum operating temperature in cooling DB 35 C WB 24 C ...

Страница 2: ...ard by a buzzer sounding briefly both when enabling and disabling all functions The settings to be made with the remote but not mentioned must be ignored 1 ELECTRICAL ELECTRONIC COMPONENTS Vane rotary compressor with a maximum input power of 1 3kW Inom max 6 A Isp max 25A 4 speed centrifugal fan motor with a maximum input power of 200W IR remote control with Olimpia Splendid serial protocol Unico ...

Страница 3: ...ay unit in the latter case the key performs this function only when the machine is working and there are no ongoing malfunctions When the corresponding LED turns on DL1 it means this mode is active and all the outputs are off In this condition by pressing the STANDBY key again on the remote or the key on the display all the previously selected functions are reset operating mode set point fan speed...

Страница 4: ...value Scala_m hysteresis Hy and scale point steps Step can be set during programming Activation of the compressor must be after a minimum Rest_time 180sec after powering of the circuit or after a previous compressor switch off All the malfunctions that are expected for the machine are enabled in this status 5 DEHUMIDIFIER MODE Selectable only with the remote control It works very much like cooling...

Страница 5: ...lay unit with LED DL3 The remote control communicates the current time to the board in question at each transmission The latter stores the current time in the eeprom every 10 minutes so in the event of a blackout besides its actual duration machine activation times are no more than 10 minutes Machine functioning mode will be that corresponding to the activation mode 9 SPECIAL FUNCTIONS DIAGNOSTICS...

Страница 6: ...1 second ON 1 sec OFF WIRING DIAGRAM A1 Electronic power board A2 Electronic command board B1 Thermostat probe F1 Compressor thermal protection K1 Relay for compressor K2 Relay for fan MED K3 Relay for fan MAX K4 Relay for fan MIN M1 Compressor M2 Fan M3 Condensate discharge pump S1 Safety micro switch S2 Pump micro switch T1 Transformer X1 General power supply terminal board X2 4 pole connector X...

Страница 7: ...ISS0011R10_A_EN doc ...

Отзывы: