21
English
Make ground connection prior to any other electrical
connections.
˄ƙƾƖʾˁƿ
!LLlELDELECTRICALCONNECTIONSARETHERESPONSIBILITYOF
the installer.
WARNING: Make water connections before electrical
connections.
Unit
4
6
8
12
15
12
15
ÇϽÊËÍÈÈÄÑ
V- ph - Hz
230 - 1 -50
400 - 3N - 50
Allowable Voltage Range
V
207 ÷ 253
376 ÷ 424
¹ÐÁÅÍÅÈÇϽʼʹÏÆ
kW
1.65
2.0
2.7
3.85
4.2
6.5
6.5
¹ÐÁÅÍÅ»ÍÊʽÆ̼ʹÏÆ
A
9
11
14.5
20.7
22.6
11.1
11.1
Power Fuses
Type
gL Type
Current
A
10 - Type B
16 - Type B
16 - Type B
25 - Type D
25 - Type D
16 - Type B
16 - Type B
ÇϽÊËÍÈÈÄÑ»¹ºÄ½Ë
mm²
H07RN-F 3 x 2.5 mm
2
H07RN-F 5 x 2.5 mm
2
¹ÐÁÅÍÅÍÊʽÆÌÐ̽ÊƹÄ
Pump Circulation
A
2
Use cables H03VV-F 4x0.75 mm
2
to connect the control to wire B0813 programmable thermostat and H03VV-F 6x0.75 mm
2
to connect the control to wire
B0812 remote control.
Also check the supply voltage and frequency of the indoor unit.
The unit can be controlled and set via:
• User Interface wire control B0813
• Wire remote control B0812 (optional)
• Switches (not supplied)
For the electrical connections refer to Figure 14, while, for
use, refer to the respective manuals.
NOTE: The quality of the contacts must be greater than
25mA @ 12V.
Remove the front panel, the electric parts appear at the
front side.
The power supply cables can be inserted into the pipe
HOLES"ESURETOlXTHEPOWERCABLEWITHBUNDLINGBAND
sold in the market so that they do not make contact with
the compressor and the hot pipes.
To ensure good tensile strength, the electric cables must be
fastened using the cable-holder on the plate.
(Only for sizes 12 and 15 use the strain relief supplied with
THEUNIT 3EElGFORPOWERSUPPLYCABLING
Wired control
For installation of wired remote controller please refer to the control installation manual.
Power supply
Size the cable, the cables must be H07 RN-F type.
According to the installation instructions, all devices for disconnection from the power supply mains must have a contact opening (4 mm) to
allow total disconnection according to the conditions provided for the overvoltage class III.
To prevent any risk, the power cable must only be replaced by the technicians of the after-sales service.
WARNING
ÇÊÌÀ½ˀÀÍÆÁÌ˺½ËÍʽÌǹÌ̹»ÀÌÀ½ÈÊÇÎÁ¼½¼»Ä¹ÅÈŲÄ̽ÊƼʾʾƽÌÇÌÀ½ÈÇϽÊËÍÈÈÄÑÏÁʽÁÆÇʼ½ÊÌÇ»ÇƾÇÊÅÌÇË̹Ƽ¹Ê¼ƖƼ½½Ų¿ʾˁƽƖ
Содержание Sherpa Monobloc 12
Страница 1: ......
Страница 6: ...6 10 1 2 4 6 7 3 6 5 5 2 4 1 7 3 9 1 2 3 1 2 3 7 6 5 2 1 4 3 4 7 1 2 3 6 5...
Страница 7: ...7 11 1 1 2 3 3 4 6 5 7 8 9...
Страница 9: ...9 13 C B 12 kW 1Ph 4 6 8 kW 1Ph 12 15 kW 3Ph 15 kW 1Ph C D A D C E A C E A D C...
Страница 95: ......
Страница 96: ...278984A...