3 REPAIR TO INTRINSICALLY SAFE COMPONENTS 

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that 

this will not exceed the permissible voltage and current permitted for the equipment in use. 

Intrinsically safe components are the only types that can be worked on while live in the presence 

of  a  flammable  atmosphere.  The  test  apparatus  shall  be  at  the  correct  rating.  Replace 

components only with parts specified by the manufacturer. Other parts may result in the ignition 

of refrigerant in the atmosphere from a leak. 

4 CABLING 

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp 

edges or any other adverse environmental effects. The check shall also take into account the 

effects of aging or continual vibration from sources such as compressors or fans. 

5 DETECTION OF FLAMMABLE REFRIGERANTS 

Under no circumstances shall potential sources of ignition be used in the searching for or 

detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) 

shall not be used. 

6 LEAK DETECTION METHODS 

The following leak detection methods are deemed acceptable for systems containing 

flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, 

but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall 

be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of 

ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and 

the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are 

suitable for use with most refrigerants but the use of detergents containing chlorine shall be 

avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak 

is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found 

which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by 

means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen 

(OFN) shall then be purged through the system both before and during the brazing process. 

7 REMOVAL AND EVACUATION 

When breaking into the refrigerant circuit to make repairs – or for any other purpose – con- 

ventional procedures shall be used.However, it is important that best practice is followed 

since  flammability  is  a  consideration.  The  following  procedure  shall  be  adhered  to:  remove 

refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas; open the circuit 

by cutting or brazing.The refrigerant charge shall be recovered into the correct recovery cylinders. 

The system shall be “flushed” with OFN to render the unit safe. This process may need to be 

repeated several times.Compressed air or oxygen shall not be used for this task. Flushing shall 

be  achieved  by  breaking  the  vacuum  in  the  system  with  OFN  and  continuing  to  fill  until  the 

working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. 

This  process  shall  be  repeated  until  no  refrigerant  is  within  the  system.  When  the  final  OFN 

Содержание COMFORT 14E

Страница 1: ...INSTRUCTION FOR USE AND MAINTENANCE EN COMFORT 14 E Caution risk of fire...

Страница 2: ...reness 1 2 Name of Parts 12 3 Accessories 13 4 Appearance and Function of Control Panel 14 5 Appearance and Function of Remote Control 15 6 Operation Introduction 16 7 Installation 19 8 Maintenance 22...

Страница 3: ...room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware the refrigerants may not contain...

Страница 4: ...sued by an accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry Repairs must be performed based on the...

Страница 5: ...d the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision 13 This appliance is not intended for use by persons i...

Страница 6: ...cification 22 Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the s...

Страница 7: ...adequately sealed or intrinsically safe 1 5 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts propriate fire extinguishing equipm...

Страница 8: ...f a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is n...

Страница 9: ...uipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas 25 maximum is confirmed Leak detection flui...

Страница 10: ...and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become fa...

Страница 11: ...der and the relevant Waste Transfer Note arranged Do not mix refrigerants in recovery units and especially not in cylinders If compressors or compressor oils are to be removed ensure that they have be...

Страница 12: ...k is possible Discharge capacitors in a way that won t cause any spark The standard procedure to short circuit the capacitor terminals usually creates sparks Reassemble sealed enclosures accurately If...

Страница 13: ...gerant circuit Purge the refrigerant circuit with nitrogen for 5 min Evacuate again Cut out the compressor and drain the oil Transportation marking and storage for units that employ flammable refriger...

Страница 14: ...l not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 2 Name of Parts Fig 1 1 Louver 6 Drainage...

Страница 15: ...tity Exhaust hose 1 Housing adaptor 1 Window Connector 1 Remote Controller 1 Window Slider Kit 1 After unpacking please check whether the above mentioned accessories are included and check their purpo...

Страница 16: ...ance and Function of Control Panel A Power on off 1 Cooling B Fan speed 2 Dehumidifying C Temperature up 3 Fan D Temperature down 4 High fan speed E Operation mode 5 Medium fan speed F Timer on off 6...

Страница 17: ...rol Remote Control Notes Do not drop the remote Do not place the remote control in a location exposed to direct sunlight 1 POWER Power on off 2 TIMER Timer on off 3 MODE Operation MODE 4 TEMP Temperat...

Страница 18: ...ction 1 Find a place where there is power supply nearby 2 As shown in Fig 5 and Fig 5a install the exhaust hose and adjust the window position Fig 5 Fig 5a 3 Insert the power cord into a grounded AC22...

Страница 19: ...ply is AC220 240V 50Hz 6 2 Cooling operation Press the Mode button until the Cool icon appears Press the DOWN or UP button to select a desired room temperature 16 31 Press the SPEED button to select f...

Страница 20: ...LEEP button again can cancel the setting 6 7 Water drainage Water Full Alarm The inner water tray in the portable air conditioner has one water level safety switches it controls the water level When w...

Страница 21: ...nd stable surface Don t block the air outlet ensure clearance of 30 cm on all sides See Fig 8 Do not install in wet areas such as bathrooms laundry etc Socket wiring should be in accordance with the l...

Страница 22: ...e Fig 9 Window Kit Installation The window kit can be installed in a vertical or horizontal position As shown Fig 10 and Fig 10a check the min and max size of the window before the installation 1 Inst...

Страница 23: ...tray inside the portable air conditioner monitors the water level When the water level reaches capacity the water full indicator lights up When the water reservoir is full remove the rubber plug at th...

Страница 24: ...gged with dust dirt the air filter should be cleaned once every two weeks Remove Filter Open the air inlet grille and take off air filter Cleaning Clean the air filter with neutral detergent in lukewa...

Страница 25: ...aust air hose is not connected or blocked Connect or clean the exhaust air hose Temperature setting is too high Reset the temperature Air inlet is blocked Clean the air inlet 3 Noisy The ground is not...

Страница 26: ...be of acceptable quality and the failure does not amount to a major failure If you have any queries regarding your product or its warranty please find contacts below I nostri prodotti sono forniti di...

Отзывы: