Page
1 from
3
Thank you for purchasing this product of
Battery charging
Olympia
Electronics. A European manufacturer.
The battery charging is completely controled
.
In
this case, is
achieved the perfect battery
GENERAL
maintenance
,
as well as the elongation of its
The luminaire consists mainly from two parts,
duration
.
When the battery has completely
the body, where all the electronics are located
charged
,
it charges with a maintenance current.
and the lamp-head where the indication sign
and the high efficiency LEDs are located.
Manual
Test
The manual test can be conducted only if the
Maintained to non-maintained selection
main power supply and the battery is
capability
connected. By pressing the test button briefly
Power on the device and press continuously
an operation test is initiated. During this test
the TEST button for 10 seconds, until the led
period all indication LEDs are OFF.
strip turns off. Release the button and after a
short emergency test, the device operates as
Automatic test
non-maintained. If you want to restore the
This test includes all the operations that
previous condition (maintained operation),
provide the manual test and is conducted
press continuously the TEST button for 10
automatically every 15 days. In order to be
seconds, until the led strip lights. Release the
performed, the main power supply and the
button and after a short emergency test, the
battery should be connected
device operates as maintained illumination
sign.
Automatic Autonomous Test
The Automatic autonomous Test is conducted
Installation
and measures the luminaire`s back up
To install the illumination sign follow the
operation. This test is conducted automatically
installation instructions on page 2.
every six months
.
In order to be performed, the
main power supply and the battery should be
Battery Cut-off
connected (the battery should be charged)
.
If
The luminaire enters in this operation when the
the battery is not charged
,
the test is
mains power supply fails
and battery has lost
postponed
until the battery is completely
its energy
.
During this operation the luminaire
charged. If during the Automatic Autonomous
enters the idle state
and battery consumption
Test the luminaire’s duration is lower than the
is negligible, in order to be protected from deep
named, then the battery must be replaced.
discharge.
SELF TESTING MAINTAINED ILLUMINATION SIGNS WITH WHITE LED’s
SLD-34/SP
SLD-44/SP
SLD-28/SP
220-240V AC/50-60Hz
3h
24h
Overcharging and full discharging protection
Charge LED, Lamp LED, Fault LED
IP 30
3.6V/1.5Ah
85lm /85lm
105lm /105lm
9.5 VA
9 VA
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3,
EN 1838
0
40 C
o
to
up to 95%
Bayblend FR3010
,
aluminum
,
plexiglas
280x120x15mm
3 years
(1
year for the battery
)
790gr.
1110gr.
1580gr.
340x190x15mm
440x240x15mm
289x65x34mm
TECHNICAL CHARACTERISTICS
Operation temperature range
Relative humidity
Construction materials
External panel's dimensions
External unit’s dimensions
Typical weight
Guarantee
Mains voltage
Maximum power consumption
Battery (Ni-MH)
Recharging time
Battery protection
Indications
Minimum emergency duration
Degrees of cover protection
Produced in accordance with
Light source intensity (230V) / (emerg.)
High Quality European based Manufacturers
922044006_09_0
20