9-30 V
Jumper required if using
a single power source.
DI COM
9.
Dry Contact Output
11. Digital Level Output - Active Low
+
-
9-30 V
Jumper required if using
a single power source.
Open-drain with +5 V internal pull-up
Vout max = 4.7 V
Open/Off = 4.7 V
Closed/On = 0 V
DI
COM
Digital Level Input
Internal pull-up
12. Digital Level Output - Active Low
+
-
9-30 V
Jumper required if using
a single power source.
If the Digital Input requires higher
than 4.7 V, use an external pull-up
resistor (10 K, up to 30 V max)
Open/Off > 4.7 V
Closed/On = 0 V
DI
COM
Digital Level Input
10 K
External pull-up
+
+
-
-
9-30 V
Jumper required if using
a single power source.
COIL
VIN
COM
PLC Voltage Input
Relay
10. Digital Level Output - Active High
1.661.
7
16.5100 [email protected]
©2019 OleumTech Corporation. OleumTech is a registered trademark of OleumTech Corporation. Other trademarks are the property of their respective owners.
Specifications, design, and product descriptions subject to change without notice. Doc ID: AD-1089-001_A