![OleumTech WIO RM1K Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/oleumtech/wio-rm1k/wio-rm1k_wiring-diagrams_3736527001.webp)
All inputs and outputs
on I/O Modules provide
field isolation.
Please wire accordingly.
TYPE POWER CONSUMPTION
RADIO 35 mA @ 12 Vdc AVG
(10% Duty Cycle)
DIGITAL 26 mA @ 12 Vdc MAX
4-20 mA 83 mA @ 12 Vdc MAX
0-10 V 58 mA @ 12 Vdc MAX
Always disconnect power
when attaching or detaching
I/O Module(s) to or from
DataRail to avoid damage.
2. Power Consumption
1. Isolation vs Non-Isolation
If isolation is required, then separate
power sources are required for
Radio Module and I/O Module(s).
If isolation is not required, a jumper
is required to make common with
Radio Module’s power supply to
to one of I/O Module’s COM pin.
+
-
9-30 V
Jumper required if using
a single power source.
1.661.
7
16.5100 [email protected]
©2019 OleumTech Corporation. OleumTech and WIO are registered trademarks of OleumTech Corporation. Other trademarks are the property of their respective owners.
Specifications, design, and product descriptions subject to change without notice. Doc ID: AD-1089-001_A
WIO
®
System Wiring Diagrams for Radio Kit RM1K
A
P
PL
IC
A
T
IO
N
D
R
A
W
IN
G