7-
Specifications
35
Line length (use with MX 43)
The following table summarizes the maximum line lengths to be used according to
the cross-section and number of sensors connected to a MX 43 controller.
TOX and O
2
With any MX 43 mother board version
Distance in meters
Line cross-section
Number of OLCT 10N detectors used to
detect toxic gases or oxygen (except CO
2
versions)
0.75 mm²
(AWG 18)
0.5 mm²
(AWG 20)
0.22 mm²
(AWG 24)
10
1000
1000
1000
20
1000
1000
900
25
1000
1000
500
32
1000
800
300