7 – Menus
51
Table 14: Relay and logic input file messages.
4. Working conditions records
This displays the actions carried out on the MX43 (simulation mode, calibration
mode, programming mode, release request, operation on internal battery), as well
as the date and time of beginning and end of the event.
Delete
allows for the deletion of this entire monitoring file. Up to 512 events can
be memorized. Beyond that, the the most recent event deletes the oldest.
Previous page, Next page,
and
Last page
allow access to the corresponding
pages of the file; each page can display a maximum of 8 lines.
Message
Significance
Lines On/Off
Start or stop the line
Detectors On/Off
Start or stop the detector
External ack
Press the external acknowledgement button
MX43 ack
Acknowledgement by the acknowledgement button on the front face of
MX43
Simulation
Switch to simulation mode
Calibration
At least one of the detectors is selected in calibration mode.
Test detectors
Switch to test mode
Program
Programming done on MX43
Time settings
Time settings on MX43
Line 1 On/Off
Start or stop line 1
Line 2 On/Off
Start or stop line 2
Line 3 On/Off
Start or stop line 3
Line 4 On/Off
Start or stop line 4
Line 5 On/Off
Start or stop line 5
Line 6 On/Off
Start or stop line 6
Line 7 On/Off
Start or stop line 7
Line 8 On/Off
Start or stop line 8
Table 15: Operation monitoring file messages.
5. Hardware troubles records
This displays, for each material incident detected: incident ID, status (activated =
ON or deactivated = OFF) as well as the date and time of occurrence or release of
the event.
Previous page, Next page,
and
Last page
allow access to the corresponding
pages of the file: each page can display a maximum of 8 lines.
Message
Significance
DEAD
Digital module no longer responding (line cut, module failure, wrong address,
module absent).
MODUL
Configuration or module address error.
TEMP+
Internal temperature of the MX43 higher than maximum tolerated value.
TEMP-
Internal temperature of the MX43 lower than maximum tolerated value.
BAT
Switching to external power supply.
LINE 1
Incident on line 1 (short-circuit).
LINE 2
Incident on line 2 (short-circuit).
Содержание MX 43
Страница 3: ...Introduction to the Application 3...
Страница 14: ...14 MX43 User manual...
Страница 24: ...24 MX43 User manual...
Страница 42: ...42 MX43 User manual...
Страница 56: ...9 Certificate of Compliance 56 Chapter 9 Certificate of Compliance...
Страница 59: ...Locking Wall mounted version by 2 locks with a key Rack version none...
Страница 63: ......
Страница 66: ...66 MX43 User manual...
Страница 67: ......