20
MX 32
Instruction Manual
-
: increasing alarm.
-
: decreasing alarm.
■
Confirm by pressing
(
MENU/ENTER
).
Defining alarm acknowledgment (manual/automatic)
■
To proceed directly to the next step, press
(
MENU/ENTER
).
■
Press
(
-
) or
(
+
) to define the
AL1
alarm acknowledgment.
-
MAN
:
(
-
). Alarm clearing
(acknowledgment) by pressing the
(
+
) button once the measurement is
below the programmed alarm
threshold.
-
AUT
:
(
+
). Automatic alarm clearing
(acknowledgment) once the
measurement is below the programmed
alarm threshold.
■
Confirm by pressing
(
MENU/ENTER
).
Defining the time delay for triggering alarm relays
■
Press
(
-
) or
(
+
) to define the 4 digits
for the time delay (in minutes, seconds)
once the
AL1
alarm relay is engaged.
Confirm the 4 digits by pressing
(
MENU/ENTER
)
Example: the value 10.20 indicates a delay
of 10 minutes and 20 seconds.
Defining the AL2 alarm threshold
■
Follow the same instructions for the
AL2
alarm threshold. Comply with the above
paragraphs
Defining the AL1 alarm
threshold
to
Defining the time delay for
triggering alarm relays
.
Defining the time delay at start-up
■
Press
(
-
) or
(
+
) to define each of
the 4 digits for the time delay (in minutes,
seconds). Confirm the 4 digits by
pressing
(
MENU/ENTER
)
Example: the value 10.20 indicates a time
delay at start-up of 10 minutes and 20
seconds.
Alarm threshold
exceeded
LED alarm
and buzzer
Delay
Alarm relay
switching
Содержание MX 32