WIRING INSTRUCTIONS 

 

 

Figure 1. Terminal numbering scheme 

 

General 

The system requires 24V AC @ 500mA supply voltage.  Since the outputs use the same power 
source, installer ought to select a proper supply power rate by taking the relay/contactor coil 
total  current  requirements  into account. For a  typical cube relays/contactor combination, 
minimum   power rate of 50VA transformer recommended. Using 18 gauge cable, connect the 
supply voltage to terminals 1 and 2.

 

When powering up, make sure that the both modules (controller and relay interface module) 
are connected via the data cord (cat#CAB485). Otherwise the interface module will not operate. 

Pressure switch 

If there is not efficient pressure, the system detects and power off the pump when the pre-
programmed delay timer expires.  

If no pressure switch is being used, set the delay time to ‘0’. This will disable the pressure 
feedback. If the pressure switch is being used, a connection must be made from pressure switch 
to the terminals 3 and 4 by using 18 gauge cable.

 

Relay, Contactor and/or Solenoids 

The outputs require 24V AC rated relays, contactors or solenoids. The outputs all together are 
internally hardwired to a resettable fuse rated at ~1500mA. Using 18 gauge cable; 

-  Connect pump relay coil to terminal 6,  
-  Intake coil to terminal 7,  
-  Drain coil to terminal 8, 
-  Connect opposite ends of the relay/contactor coils to terminal 5 (common). 

 

Caution 

The triac outputs should NOT be grounded and each output should NOT exceed 500mA. 

 

 

 

 