oke-2012 user manual V19-9 en.PDF
User mode function Setup
User mode function
Function
Temp.
Display
Operating range
Maker
value
Operating Temp.
setup
10.0
LSP∽HSP
10.0
℃
1.
Press “SET” button shortly.
2.
After adjust Temp. with Up / Down button, press “SET” button.
3. Save the new Temp. and complete the setup.
Setup process
Function
Display
Operation range
Maker value
Max.Temp set
HSP
-
40.0 ∽99.9℃
99.9
℃
Min.Temp. set
LSP
-
40.0 ∽99.9℃
-40.0
℃
Output
Delay-time
dlt
0∽9 분
0
분
Output
deviation
dif
0.1 ∽9.0℃
1.0℃
Output Temp.
correction
Cor
-
9.9 ∽+9.9℃
0.0℃
Output mode
typ
C(Cooling)∽H(Heating)
C(Cooling)
Emergency
operating time
SCL
ON
time ∽ OFF
time
autosave
Master Mode function Setup
※
Emergency operating mode function setup
※
1. (Emergency operating (SCL)) : When the temp sensor is not stable, the temp
control function will transfer automatically to timer control function, and it
will work the current temp control system as close as possible.
2. (emergency operating time) when it return to normal operating system after
first time or initialized emergency operating time , it will store the operating
time after calculating the average time based on 3 times of relay ON/OFF.
During calculating the average time, “1 indicate” will blinking as below
picture and will turn off the indicate when it completed the time (once the
emergency operating time is stored, it will remain even if power is off)
3. (emergency operating confirm) when emergency operating is in activating,
the “2 indicate” as below picture will ON and display “AUt” with blinking at
temp display window. In order to confirm the ERROR message, it should be
initialized the emergency operating time.
4.
(emergency operation time confirm) after one time press the “SET” button, it
can reconfirm the time thru press “↑” button will display “relay ON time”
and press”↓” button will display “relay OFF time”
5. (Initialize the emergency operating time):
a.
when press over 5 seconds “↑” or “↓” button, time will complete the
initialization.
b. initialing with net Output mode.
c. initializing with new set temp..
Emergency lamp indicator
Emergency recoding indicator
After converted to “HSP” mode, press
“SET” button.
Adjust with Up / Down button, press
“SET”
button
After converted to “LSP” mode, press
“SET”
button
Return to normal Temp. display
mode
Press “SET” button during 5 seconds,
then convert to master function mode.
Adjust with Up / Down button, press
“SET”
button
After converted to “dlt” mode , press
“SET”
button
Adjust with Up / Down button, press
“SET”
button
After converted to “dif” mode, press
“SET”
button
Adjust with Up / Down button, press
“SET”
button
After converted to “Cor” mode, press
“SET”
button
Adjust with Up / Down button, press
“SET”
button
After converted to “typ” mode, press
“SET”
button
Adjust with Up / Down button, press
“SET”
button
After converted to “SCL” mode, press
“SET”
button
Adjust with Up / Down button, press
“SET”
button during 5 seconds
Master Function mode setup process
Specification
Control Output range depend on Output
deviation setting ( Cooling mode )
SET
Temp.
10
℃
Output ON
Output OFF
Output OFF
Output ON
➢
Operation range : -55.0
℃
~99.9
℃
➢
External size (mm) : 76(W) x 34(H) x 75(D)
➢
Cutting size (mm) :70(W) x 30(H)
➢
Delay time : 0 ~ 9 MIN (1min/unit)
➢
Correct Current Temp. : -9.9~+9.9
℃
(0.1
℃
/units)
➢
Input sensor : NTC (5K
Ω 25
℃
) sensor
➢
Sensor accuracy : 1 %
➢
Power supply : 230VAC 50/60Hz
➢
Power Consumption : Aver. 5VA
↓
➢
Ambient temp./ Humidity : 0
℃
~50
℃
/ 80%
↓
➢
Output : 1 relay ON/OFF (250VAC 2A)
➢
Output deviation : 0.0
℃
~9.0
℃
(0.1
℃
/units)