![OJ Electronics WLCT2 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/oj-electronics/wlct2/wlct2_user-manual_727378014.webp)
14
u
sing cooling functions
Master
settings
Factory settings
Ba/Fs
Cooling mode
Day cooling temperature
Day heat tempe 3°C
Night cooling temperature
Day cooling tempe 3°C
DEW point safety zone
DEW point + 3°C
Room temperature control
PI - control
P = 4°C
I = 90-180 sec
k-factor = 0.1
Floor Limit temperature control
P - control
P = 4°C
Adaptive PWM control
Max allowed Room temperature fluctuation
+/- 0.5°C
Self adjusting (adaptive) PWM time interval limits
15 – 45 minutes
Max number of connected
sensors
Wired and wireless
24
Sensor timeouts
Wired
300 sec. (5 min)
Wireless
10000 sec. (2h 45 min)
Fs
Minimum cooling supply water temperature
16°C
Supply water temperature
control
PI - control
P = 20°C
I = 300 sec.
k-factor = 0.05
Additional information