background image

I N S T R U C T I O N S

© 2021 OJ Electronics A/S

67273C 04/21 (PBV)

PTH-6201-DF

• English
• Deutsch
• Français

English

LIST OF FIGURES

The following figures are located at the back of 

the instructions:

Fig. 1:  Dimensioned drawing

Fig. 2:   Position of transmitter in relation to 

bends and branches

Fig. 3:  Wiring diagram, PTH-6201-DF

Fig. 4:  Example of configuration

Fig. 5:  Orientation of PTH

INTRODUCTION

PTH-6201-DF is an electronic pressure trans-

mitter which communicates via Modbus and is 

primarily used to measure differential pressure 

in a ventilation system. The pressure transmitter 

is used in connection with monitoring, control 

and regulation via an electronic controller, i.e. in 

PLC, BMS or SCADA systems. All commands 

and data exchanged between the PTH-6201-DF 

and the control unit are sent as digital values via 

Modbus protocol. The integrated Modbus com-

munication makes the PTH-6201-DF highly suit-

able for integration into PLC, BMS and SCADA 

systems by reducing installation costs.

Typical applications include:

-   Measurement of pressure at a given point in a 

ventilation system.

-   Measurement of differential pressure across 

a ventilation filter for optimum filter replace-

ment.

-   Measurement of differential pressure across a 

fan for the regulation of duct pressure.

FUNCTION

PTH-6201-DF is a pressure transmitter for 

comfort or process ventilation. It communicates 

via Modbus with a connected control unit (see 

fig. 4), and displays, via Modbus communica-

tion, a value dependent on the measuring range 

set in the control unit, which is proportional to 

the measured pressure. PTH-6201-DF uses a 

semiconductor pressure element with no air 

throughput, thus protecting the unit from dust in 

the ventilation system. The pressure element is 

temperature compensated to provide accurate 

pressure measurement throughout the specified 

temperature range. See ‘Technical Data’.

INSTALLATION

The housing is opened without the use of tools 

by pressing the snap lock at the side of the tube 

connectors.

PTH-6201-DF should be attached to a firm, lev-

el surface using two screws. PTH-6201-DF can 

be installed in any orientation without affecting 

its accuracy. PTH-6201-DF also functions with 

only one tube fitted to the tube connectors (+ or 

-). However, two tubes should always be fitted 

to maintain the enclosure rating unless the tube 

connectors face downwards. 

Pressure is supplied to the measurement unit by 

tubes, the higher pressure being connected to 

the ‘+ tube connector’ and the lower pressure 

to the ‘÷ tube connector’ (see fig. 3). 

The pressure tubes must be as short as pos-

sible and must be secured in position to prevent 

vibration. 

To obtain the best possible results, pressure 

must be measured where there is least risk of 

turbulence, i.e. in the centre of the ventilation 

duct and at a distance of at least twice the 

width of the duct from bends and six times the 

width from branches (see fig. 2).

If there is a risk of condensation forming in the 

tubes, PTH-6201-DF must be positioned in 

such a way that condensate cannot flow back 

into the pressure transmitter.

The housing is equipped with screw holes (see 

fig. 1).

Modbus cable connection

The housing is opened without the use of tools 

by pressing the snap lock beside the tube con-

nectors. 

Modbus is connected to PTH-6201-DF via the 

four screw terminals, which besides being used 

for Modbus connection are also used for loop 

connections to other Modbus components in 

the application. PTH-6201-DF must be provided 

with a 24 V DC power supply connected to 

screw terminals 1 (+) and 4 (GND), see fig. 3.

Settings

PTH-6201-DF can function either as a pres-

sure transmitter or as an air flow recorder. The 

buttons beneath the cover are used to switch 

between these two functions.

Use buttons 

 and 

 to select function. Con-

firm with the 

OK

 button.

Pressure transmitter

When 

PA

 flashes on the display, confirm the 

selection with the 

OK

 button. PTH-6201-DF 

now functions as a pressure transmitter.

Air flow recorder

When 

Flo

 flashes on the display, confirm the 

selection with the 

OK

 button. A k-factor must 

then be specified. The first digit on the display 

flashes. The value can be changed using but-

tons 

 and 

 .

Confirm the setting with 

OK

 and the next digit 

flashes. Repeat the procedure to set all four dig-

its. Once the last digit has been confirmed, use 

the same buttons to position the decimal point. 

Confirm the position with the 

OK

 button. PTH-

6201-DF now functions as an air flow recorder.

Changing the unit of flow

The unit shown depends on the k-factor speci-

fied. The unit can be changed by affixing the 

self-adhesive label with the correct unit onto the 

front foil.

Measuring range, pressure

PTH-6201-DF switches automatically to the 

optimum pressure range.

Measuring range, flow

  1.00 m ³/s 

100.0 m³/h  30.00 m³/h x 1000

  3.00 m³/s 

300.0 m³/h  50.00 m³/h x 1000

  5.00 m³/s 

500.0 m³/h  99.99 m³/h x 1000

  10.00 m³/s 

1000 m ³/h

  30.00 m³/s 

3000 m ³/h

  50.00 m³/s 

5000 m ³/h

 100.00 m³/s 

9999 m ³/h

The units m³/h and m³/s can be replaced by l/s.

k-factor can be set from 0.001 to 9999. 

TECHNICAL DATA

Supply voltage .............. 24 V=, ± 15% via Modbus

Power consumption .......................................0.5 W

Measuring range Pressure ......................0-2500 Pa

Maximum pressure ....................................... 30 kPa

Accuracy* ..................................0.5 %×MV*+2.5 Pa

Modbus protocol ................38.4 kBaud, 1 start bit,

 

8 data bits, 1 stop bit

Cable dimension ......................................Ø3-10mm

Housing dimensions (h×w×d) .......... 91×75×38mm

Connection

4 x Screw term, max 1.5mm²

Pressure tubes .....................................2 × ø6,2 mm

Environment data

Storage temperature .......................-40°C to +70°C

Operating

temperature.............. -20°C to+40°C (continuous)**

 

-30°C to +70°C (short-term)***

Operating 

humidity .......10%RH to 95%RH, non-condensing

Operating altitude .......................................≤2000m

Enclosure rating ................................................ IP54

Weight ............................................................. 110 g

*Note: MV = Measured Value

**Note: Ambient temperature affects the LCD 

display speed and contrast

***Note: DC Supply is recommended if the 

operation temperature exceed 40°C 

OPERATION

Status LEDs in normal operation:

”Power ON” (green LED) lights up to indicate 

that voltage is received via the Modbus cable. 

Valid communication on Modbus is similarly 

indicated by a ”Modbus Communication” (yel-

low LED) which flashes, the intensity of flashing 

being dependent on communication intensity.

LED

ON

FLASHES

OFF

Green

Power 

ON

Power OFF

Yellow

Valid Modbus 

communication

Invalid Modbus 

communication

Modbus protocol

PTH-6201-DF has an addressing area of 16 and 

can be set for the addresses between 0x50h 

and 0x5Fh. The address can be set on the ad-

dress switch inside the PTH-6201-DF.

Modbus addresses 

Encoder - ID

 

0 - 0x59 (89 dec) 

8 - 0x53 (83 dec)

 

1 - 0x56 (86 dec) 

9 - 0x54 (84 dec)  

 

2 - 0x50 (80 dec) 

A - 0x5A (90 dec)

 

3 - 0x51 (81 dec) 

B - 0x5B (91 dec)

 

4 - 0x57 (87 dec) 

C - 0x5C (92 dec)

 

5 - 0x52(82 dec) 

D - 0x5D (93 dec)

 

6 - 0x58(88 dec) 

E - 0x5E (94 dec)

 

7 - 0x55(85 dec) 

F - 0x5F (95 dec)

Содержание PTH-6201-DF

Страница 1: ...ap lock beside the tube con nectors Modbus is connected to PTH 6201 DF via the four screw terminals which besides being used for Modbus connection are also used for loop connections to other Modbus co...

Страница 2: ...en und so zu befestigen dass Schwingun gen vermieden werden Mit R cksicht auf eine optimale Druckmessung ist die Messung dort vorzunehmen wo die ger ingste Gefahr turbulenter Str mung vorhanden ist da...

Страница 3: ...auschen Messabweichung Die Umgebungstemperatur des PTH 6201 DF liegt au erhalb des angegebenen Temperatur bereichs Umgebungstemperatur an den in dieser Anleitung angegebe nen Bereich anpassen Fehlende...

Страница 4: ...fix sur une surface solide et de niveau avec deux vis Le PTH 6201 DF peut tre mont dans toute orientation sans affecter d favorablement sa pr cision Le PTH 6201 DF fonctionne galement avec seu lement...

Страница 5: ...ur des adresses entre 0x50h et 0x5Fh L adresse peut tre r gl e par les interrupteurs d adresse l int rieur du PTH 6201 DF Adresses Modbus Encodeur ID 0 0x59 89 dec 8 0x53 83 dec 1 0x56 86 dec 9 0x54 8...

Страница 6: ...ig 2 Position of transmitter in relation to bends and branches BR956A03 BR0875A02 PTH Regulator PTH Fig 4 Example of configuration BR875A02 PTH BR956B15a Fig 3 Wiring diagram PTH 6201 DF 2021 OJ Elect...

Страница 7: ...2021 OJ Electronics A S 7...

Страница 8: ...ark is registered and belongs to OJ Electronics A S 2021 OJ Electronics A S 8 OJ ELECTRONICS A S Stenager 13B DK 6400 S nderborg Tel 45 73 12 13 14 Fax 45 73 12 13 13 oj ojelectronics com www ojelectr...

Отзывы: