CS4

TM

 THERMOSTAT

A wireless, radio controlled thermostat recom-

mended for Comfort System 4. The thermostat 

is ideal for all floor types and controls the 

heating on the basis of room, floor or room/floor 

limit temperature. Wireless communication to 

the central controller ensures easy installation.

The thermostat is for flush mounting in a wall 

socket. A baseplate for external wall mounting 

is available.

PRODUCT PROgRAMME

MSD4-1999-UA   Radio controlled thermostat 

with built-in room sensor and 

floor sensor

WARNINg

 – Important Safety Instructions 

Disconnect the power supply before carrying 

out any installation or maintenance work on this 

unit and associated components. This unit and 

associated components should only be installed 

by a competent person (i.e. a qualified electri-

cian). Electrical installation must be in accord-

ance with appropriate statutory regulations.

MOUNTINg Of SENSOR

The floor sensor contains a safety extra-low 

voltage (SELV) circuit, allowing it to be placed 

as close to the floor surface as possible without 

having to take account of the risk of shock 

should the sensor cable become damaged. 

The two wires connecting the sensor to the 

mounting box must be additionally insulated, 

e.g. shrink flex. 

To prevent loose wires in the fixed installation 

from coming into contact with the terminal 

block for the floor sensor, they must be re-

strained using cable ties. 

It is recommended that the cable and sensor be 

placed in a non-conductive installation pipe em-

bedded in the floor (fig. 3). The end of the pipe 

must be sealed and the pipe placed as high as 

possible in the concrete layer. Alternatively, the 

sensor can be embedded directly in the floor. 

The sensor cable must be led through a sepa-

rate pipe or segregated from power cables.

The floor sensor must be centred between 

loops of heating cable. 

The sensor cable may be extended up to 100 

m by means of a separate two-core cable. Two 

vacant wires in a multi-core cable used, for 

example, to supply current to the floor heating 

cable must not be used. The switching peaks of 

such current supply lines may create interfer-

ence signals that prevent optimum controller 

function. If a shielded cable is used, the shield 

must not be connected to earth (PE). The two-

core cable must be placed in a separate pipe or 

segregated from power cables.

MOUNTINg Of THERMOSTAT 

WITH bUIlT-IN SENSOR

The room sensor is used for comfort tempera-

ture regulation in rooms. The thermostat should 

be mounted on the wall approx. 1.6 m above 

the floor in such a way as to allow free air 

circulation around it. The thermostat must never 

be covered by a curtain or similar. Observe the 

minimum distance from large metal surfaces, 

electronic equipment, electric motors, etc. 

(fig. 4a). To ensure good transmission, the unit 

should be placed as high as possible, min. 50 

cm above the floor (fig. 4b). Draughts and direct 

sunlight or other heat sources must be avoided 

(fig. 4). 

Mounting of thermostat 

1.  Slide the power button down to Off “0”.

2.  Release the front cover ONLY by inserting a 

small screwdriver into the hole on either side 

of the thermostat.

3.  Connect the wires in accordance with the 

diagram (fig. 2). 

4.  Mount the thermostat in the wall socket. 

Please ensure that the adapter plate is  

properly clipped on the thermostat.

5.  Fit the frame and carefully press the cover 

onto the thermostat. Ensure that both the 

power slide button on the cover and the 

power switch pin are down.

DO NOT

 open the thermostat by releasing the 

four fixing clips on the back.

SETUP

See user manual for Comfort System 4 - Central 

Controller. 

Quick guide to thermostat setup:  

1. 

Systemsettings

Activate the Master by  

pressing the Menu button 

and selecting System 

settings. 

2. 

Add to unit

Select Add to unit.  

 

 

3. Activate the thermostat to  

be set up. The thermostat 

will display its address.  

 

4. Select zone/name. 

fAUlT lOCATION

If the sensor is disconnected or short-circuited, 

the heating system is switched off. The sensor 

can be checked against the resistance table 

(fig. 5). 

ERROR CODES

E0:   Internal error. The thermostat must be 

replaced.

E1:   Built-in sensor short-circuited or  

disconnected.

E2:    External sensor short-circuited or  

disconnected.

E5:   Internal overheating. Inspect the installation.

CE MARkINg

According to the following directives: 

LVD 2006/95/EC, EMC 2004/108/EC, 

R&TTE 1999/5/EC. 

ClASSIfICATION

The product is a Class II device (enhanced insula-

tion) and must be connected in the following way: 

Term. 1:  

Neutral (N)

Term. 2:  

Phase (L) 230 V ±10 %, 50/60 Hz 

Term. 3-4:   Load, max. 16 A / 3600 W

Term. X:  

Do not connect

Term. 5-6:   External floor sensor

ENvIRONMENT AND RECyClINg

Please help us to protect the environment by 

disposing of the packaging in accordance with 

national regulations for waste processing.

RECyClINg Of ObSOlETE APPlIANCES

Appliances with this label must not be 

disposed of with general household 

waste. They must be collected 

separately and disposed of in 

compliance with local regulations.

 

TECHNICAl DATA

Voltage  .......................... 230 V AC ±10 % 50 Hz

Max. pre-fuse .............................................. 16 A

Built-in circuit breaker ....................  2-pole, 16 A

Output relay ............. Make contact - SPST - NO

Output ....................................  Max. 16 A / 3600

Control principle .................................... PWM/PI

Stand-by power ...........................................  1 W

RF frequency band .............................868.3 Mhz

RF transmission range ......100 metres/open field

Temperature range ............................. +5/+40 °C

Limit sensor  ....................................... +5/+40 °C

Ambient operating temperature .......... +0/+25 °C

Sensor input type ....................................... SELV

Pollution degree ................................................ 2

Overvoltage ............................................... Cat. II

Rated impulse voltage ................................. 4 kV

Enclosure rating ........................................  IP 21*

Dimensions .................... H/115, W/84, D/40 mm

Mounting depth ....................................... 20 mm

Display ........................ H/25, W48 mm, segment

EU Registered Design  ........  001534462-0001/2

According to EN 60730-1:2011

Automatic action type 1

* IP 21 applies only to front with cover after 

  mounting in a flush box

The thermostat is maintenance free.