OJ Electronics EFR Series Скачать руководство пользователя страница 3

© 2017 OJ Electronics A/S

3

dukten får anslutas till elnätet.

TEKNISKA DATA

Driftsspänning .... 230V AC eller 400V AC, ±10%

 

Automatisk opkoppling

Driftfrekvens ..........................................50/60 Hz

Egetförbrukning ............................................5 VA

Ingångskretslopp

Styrspänningsssignal ..0-10V DC eller 2-10V DC

 

eller 22-440V AC

Ingångsimpedans .................................> 100 kW

Styrströmsignal .......0-20 mAdc eller 4-20 mAdc

 

Spänningstopp < 3,3V DC

 

(shunt = 170 W)

Periodtid (puls/paus) ..........................ca. 45 sek.

Försörjning till extern regulator EFRP:

 

14V DC rippel/max. 15 mA

Utgångskretslopp

Fasström:

 EFM-9161 .................................... 16 A

eff

 EFM-9251 .................................... 25 A

eff

Säkring (rekommenderas):

 EFM-9161 .......................................16 A

 EFM-9251 .......................................25 A

Belastningstyp ....................... endast resistiv last

Värmeavgivning ...........................ca. 1,5 W/amp.

Överhettningstermostat ............................... 85°C

(automatisk återinkoppling när temperaturen har gått ner)

Isolationsspänning ................................2500 V

eff

Omgivningstemperatur .......................–10/+40°C

Vikt ca.  500 g

Dimensioner (se fig. 11) ...H/92, B/156, D/45 mm

Kapslingsklass ..............................................IP20

EFM-serien är underhållsfri.

MONTAGE OCH ANSLUTNING

Montage

EFM-serien monteras på vägg eller DIN-skena 

i ett styrskåp. Styrningen måste ha tillräcklig 

ventilation. Ma xi mal omgivningstemperatur vid 

maximal ef fekt be last ning är 40°C (se fig. 3 och 

4).

OBS!

 Kylflänsarna skall monteras vertikalt.

Kylprofilen kan vid max. belastning uppgå till 

85°C och får därför inte vara åtkomlig under 

drift.

Effektbelastning

Det krävs en minimumbelastning mellan faserna 

på 500 W. Vid större effektbelastning än 25 

A för typ EFM-9251 kan flera EFM-enheter 

parallell-kopplas på ingångssidan (inte på 

utgångssidan).

Styrsignal

Styrkabeln från extern regulator kan förlängas

 

upp till 50m med separat kabel.

Undvik att förlägga kabeln parallellt med andra 

kablar som kan inducera störningar på styrsig-

nalen och därmed störa styrningens funktion. 

Det är inte nödvändigt att använda skärmad ka-

bel till styrningen, men det förbättrar dock i hög 

grad styrningens immunitet mot störningar när 

den används i industriell miljö. Skärmen skall 

anslutas till plint 1 (GND).

MONTERING av styrningen (fig. 5-10)

A.  Styrningen monteras enligt beskrivning

B.  Kablarna ansluts enligt anslutningsschema  

 

fig. 5, tabell 1 och 2. 

Se eventuellt

 också  

 

EFM-tillämpningar fig. 5-7.

C.  Ställ in DIP1 och DIP2

 

se inställning av ingångsfunktion 

D.  Anslut spänningsförsörjningen

ANSLUTNINGER

Klämma  

Anslutning

  PE  

Chassi (PE)

  L1 

Nätförsörjning L1

  L2 

Nätförsörjning N 

   

(eller L2 vid 400 Vac)

  T1 

Belastning 1

  T2 

Belastning 2

Starkström (Power) Tabell 1

  Klämma  

Funktion

  1 

Jord - GND

  2 

Strömingång + (I in)

  3 

Spänningsförsörjning till

    

värmeregulator EFRP (V ut)

  4 

DC/AC Spän ning sin gång + (V in)

Styrsignal Tabell 2

FUNKTIONER

SÄKERHETSFUNKTION

En sensor vid triac-styrningens kylelement 

övervakar att det inte sker någon överhetting. 

Den stänger av styrningen om den täcks över 

av miss tag eller om omgivningestemperaturen 

överstiger tillåtet värde. Återinkoppling sker 

automatiskt när felet har eliminerats.

LYSDIODENS INDIKERING

Ljussignal Funktion

Röd (fig. 2) ......................................  Spänning till

INSTÄLLING AV INGÅNGSFUNKTION

Funktionen ställs in med hjälp av 2 DIP-omkop-

plare (fig. 2). Omkopplarna DIP 1 och DIP 2 är 

plaverade vid sidan av anslutningsplintarna 1-4 

för svagström.

 DIP1 DIP2  Ingångssignal
   

 

(Ingångsstiftets nummer)

 

OFF   OFF 

  0-10 Vdc (4-1)

   

 

24-400 Vac (4-1) 

  OFF   ON 

2-10 Vdc (4-1)

  ON 

OFF 

0-20 mA (2-1)

  ON 

ON 

4-20 mA (2-1)

FIGURER 

Figur 1.  Reglerprincip för EFM. 

Figur 2.   EFM-front med lysdiod, DIP-omkop-

plare och anslutningsplintar

Figur 3.   Belastningskurva för max. omgivning-

stemperatur EFM-9161.

Figur 4.   Belastningskurva för max. omgivning-

stemperatur EFM-9251.

Figur 5.   Spänningsanslutningsklämmor på  

EFM.

Figur 6.   Användning av AC-styrsignal vid sam-

mankoppling av 2 styrenheter med 

belastning kopplad i stjärnform

Figur 7.  Tillämpning EFRP-31 för EFM.

Figur 8.  Tillämpning EFRP-91 för EFM.

Figur 9.  Tillämpning ERZ för EFM.

Figur 10.  Tillämpning med 4-20 mA för EFM.

Figur 11.  Måttskiss för EFM.

CALECTRO AB

Svalörtsgaten 16 . S-426 04 Västra Frölunda

Tel +46 3169 53 00 . Fax +46 3129 32 91

English

APPLICATION OF THE CONTROLLER

The EFR series is applied for accurate, electro-

nic noiseless measuring. It is suitable for regu-

lation of industrial electric heating, for instance 

for floor and overhead ra di a ti on heating as well 

as for electric radiators. The controller can also 

control heating surfaces in ven ti la ti on systems 

and be used for industrial power regulation.

PRODUCT PROGRAMME

Product 

Load Type

Controller 

1 x 16 A 

EFM-9161

Controller 

1 x 25 A 

EFM-9251

Accessories EFM

Temperature regulator 

 

ERZ

Heat regulator for DIN-rail 

 

EFRP-31

Heat regulator for wall mounting   

EFRP-91

FUNCTION

The EFM series is an electronic time proportio-

nal triac controller with 1 triac with zero forward 

trigging for a one-phase net and for powers up 

to 25A.

The EFM controller is controlled by an external 

regulator, from an ERZ/EFRP regulator, or ano-

ther 0-10V DC temperature regulator.

The desired temperature is set on the external 

re gu la tor and the controller will then convert the 

control signal to a pulse/pause ratio. The triac 

exit will then add the heating effect presently 

needed.

With a 0-10V signal the EFR will at 5V be 

connected and disconnected 50% of the period 

time (see fig. 1).

The EFM controller may also be used as a boo-

ster and controlled by an ON/OFF AV voltage 

signal (see pinciple in fig. 6).

CE MARKNING

OJ declare under their own responsibility 

that this product meets the requirements of 

the European Council’s directive 89/336 and 

successive modifications as to electro-magnetic 

compatibility and the Council directive 73/23 

as to electrical equipment to be applied within 

certain voltage ranges.

Standards applied 

EN 50 081-2, EN 50 082-2 and EN 60 730-1.

The product may only be energised when the 

entire installation meets the current directive 

requirements.

When the product is installed according to this 

instructions guide and the current installation 

guidelines, it is covered by factory guarantee.

If the product has been exposed to damage e.g. 

in transport, it must be checked and overhauled 

by qualified staff before the product is connec-

ted to the grid.

TECHNICAL DATA

Working voltage......230V AC or 400V AC, ±10%

 

Automatic shift

Working frequency ................................50/60 Hz

Own consumption ........................................5 VA

Input circuit

Control voltage signal ..... 0-10V DC or 2-10V DC

 

or 22-440V AC

Input impendance ................................> 100 kW

Control voltage signal ........................ 0-20 mAdc 

 

                    or 4-20 mAdc

 

Voltage loss < 3.3V DC

 

(Shunt = 170 W)

Period time (pulse/pause) ........... approx. 45 sec.

Supply from external regulator EFRP:

 

14V DC rippled/max. 15 mA

Exit circuit

Phase current:

 EFM-9161 ................................. 16 A

RMS

 EFM-9251 ................................. 25 A

RMS

Pre-safety fuse (recommended):

 EFM-9161 .......................................16 A

 EFM-9251 .......................................25 A

Load type ............................... only resistive load

Emission of heat ..............approx. 1,5 W/Ampere

Содержание EFR Series

Страница 1: ...gulator kan forl nges ind til 50 m med separat kabel Undg at kablet l g ges parallelt med andre kabler som kan in du ce re st j p styresignalet og dermed for styrre con trol ler ens funktion Det er ik...

Страница 2: ...igt med en skj rmet kabel til effektregulatoren men det forbedrer vesentlig effektregulatorens immunitet overfor st y n r den anvendes i industrimilj Skjermen avsluttes til ter mi nal 1 GND MONTERING...

Страница 3: ...20 mA 2 1 FIGURER Figur 1 Reglerprincip f r EFM Figur 2 EFM front med lysdiod DIP omkop plare och anslutningsplintar Figur 3 Belastningskurva f r max omgivning stemperatur EFM 9161 Figur 4 Belastning...

Страница 4: ...gen wie z B Boden oder Deckenbeheizun gen sowie von elektrischen Heizk rpern Die Kontroller k nnen aber auch zur Ansteu erung von Heizfl chen in Ventilationsanlagen oder f r die industrielle Leistungs...

Страница 5: ...nneaux chauffants dans des installations de ventilation ou pour la r gulation de puissance dans des applications industrielles Gamme de produits Produit Charge nominale Type Contr leur 1 x 16 A EFM 91...

Страница 6: ...le r gulateur de chauffage EFRP V out 4 DC AC V in Signal de pilotage tableau 2 Fonctions de s curit Une sonde surveille en permanence la temp ra ture du radiateur de refroidissement du triac afin de...

Страница 7: ...2017 OJ Electronics A S 7 Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 Fig 6 Fig 7 Fig 8 Fig 9 Fig 10 Fig 11 BR834E09 BR855A11 BR855E06 BR855E05 BR855A05 BR855A09 BR855E01 BR855E04 BR855E02 BR855A03 BR855A06A...

Страница 8: ...A S 2017 OJ Electronics A S OJ ELECTRONICS A S Stenager 13B DK 6400 S nderborg Tel 45 73 12 13 14 Fax 45 73 12 13 13 oj ojelectronics com www ojelectronics com 8 Strandvejen 42 Saksild 8300 Odder 86...

Отзывы: