L
Lockout warning lamp
RAR
Flame detector
SM
Motor of sequence switch
V
Flame signal amplifier
NTC
NTC-thermistor
*) The wire link B has been cut away at the factory. This allows an automatic repetition of
start-up sequence, if the flame extinguishes during burner operation. If the wire link B has
not been cut away, lockout occurs, if the flame is extinguished during burner operation.
6.4.
6.4.
Flame Detector
Flame Detector
6.4.1
6.4.1
Technical data
Technical data
TYPE
RAR...
Min. required detector current with 230 VAC
6,5 μA
Max. permissible detector current without
flame
—
Max. possible detector current
25 μA
Instrument's +pole to terminal
22
Cable run to detector in the same cable as
control lines
not perm.
Cable run to detector with a separate cable
in cable duct
RAR7: 30 m
Shielded cable (insulated shielding)
RAR8: 100 m
Shielding to terminal
—
22
23
LAL2...
RAR...
RPMARINES 30870641GB
57 (58)
6. Technical data