5.7 Time sequence diagram, oil use, 2-stage
Time sequence diagram for oil (two stage) ver. 1
3) Irrelevance time oil P 765 affects safety interlock chain oil and oil pressure min.
when ignition valve or oil valve opens.
X07
Safety interlock chain boiler
X04
Ignition transformer
X06
Safety interlock chain burner
X01
Main oil valve and 1-stage valve
X10
Burner ON
X02
Main oil valve and 2-stage valve
X08
Monitoring air pressure
X25
Fan ON
X20 + X21
Flame signal
X24
Fault
X32
Air damper
5.8 Operation description, oil use
Prerequisites for start-up
● Fuel selector switch in position 1 (OIL).
● Failures and interlocks are reset.
● Limit switch on burner flange and oil pressure switch (X06) are closed.
● Boiler safety equipment is reset (X07: temperature and pressure limit switch, dry-
boiling preventer, boiler flange limit switch and so on).
● The control unit is on standby.
● Remote control contacts are closed (X10).
● Boiler thermostat/pressure switch contact is closed (X10).
● Differential air pressure switch contact is open (X8).
● Load controller module start-up limit reached.
Start-up
● Control unit safety features are activated.
● Fan motor is started (X25).
● Servomotors drive to the pre-purge position.
M5164 1640EN
73 (95)