Limiting domestic hot water temperature
In the winter season, the temperature in the lower section of the storage tank
is determined by the flow temperature (flow to heating circuits). As outdoor and
indoor temperatures are lower, the compressor may run for long periods of time.
Consequently, the water in the upper section of the tank can become scalding hot. The
maximum temperature limit for the compressor is 90 °C.
To prevent the domestic hot water from becoming dangerously hot, the system can be
equipped with a temperature limiter function (optional accessory).
The maximum temperature of domestic hot water can be specified in the
Hot water
temperature limiter
view. Access the view through
Heating curve selection,
see
section
Heating curves.
Domestic hot water limiter ver. 1
Adjust the limit with the plus and minus buttons next to the
Maximum temperature
field.
● Adjustment range: 0–90 °C, factory setting: 55 °C.
In the summer season when no heating is required outside wet areas, the compressor
runs infrequently, and less superheat is available for domestic hot water heating.
Consequently, the temperature in the upper and lower section of the tank are closer to
each other.
4.4.9 Accessories
The Accessories view shows a list of optional accessories and functions added to the
system.
Accessories ver. 1
36 (75)
M8010 2204EN
Содержание ESi 6-17
Страница 2: ......
Страница 62: ...Dimensional drawings ESi 10ESI14_2 ESI 1 ver 1 10ESI14_2 ESI 2 ver 1 60 75 M8010 2204EN...
Страница 63: ...Dimensional drawings EMi 10EMI28T_3 EMI ver 1 M8010 2204EN 61 75...
Страница 64: ...Dimensional drawings ELi 10ELI60T_2 ELI ver 1 62 75 M8010 2204EN...
Страница 78: ...76 75 M8010 2204EN...
Страница 79: ......