Brine circuit pump curve, ECO I
ECO I brine pump curve ver. 1
X-axis: Flow rate, m
3
/h. Y-axis: pump head, m.
0/−3 °C
Maximum brine circuit loop length
The table below provides an estimate of the maximum brine circuit loop length
supported by the brine pump. The estimate accounts for the heat pump, brine loop and
a DN 32 fill valve unit. The margin of error for the estimate is approximately 30%.
Unit
Design value,
example
Design value,
example
Brine into the evaporator
°C
0
0
Brine out of the evaporator
°C
–4
–3
Water into the condenser
°C
+30
+30
Water from the condenser
°C
+35
+35
Temperature difference across the
evaporator circuit
°C
4
3
Temperature difference across the
condenser circuit
°C
5
5
Maximum cooling capacity
kW
18.0
18.7
Maximum heating capacity
kW
23.7
24.4
Evaporator circuit flow
m
3
/h
3.97
5.50
Evaporator circuit flow
kg/h
3846
5329
Condenser circuit flow rate:
m
3
/h
4.10
4.23
Condenser circuit flow rate:
kg/h
4079
4206
1 x DN40x2.4 brine circuit loop
length
m
–
–
2 x DN40x2.4 brine circuit loop
length
m
325 m borehole,
650 m loop
(90 m borehole,
180 m loop)
M8003 2219EN
51 (54)
Содержание ECO Inverter+ 25
Страница 1: ...M8003 2219EN 24 May 2022 INSTALLATION AND COMMISSIONING ECO Inverter 7 25...
Страница 2: ......
Страница 4: ...6 7 EU Product Data 52 2 54 M8003 2219EN...
Страница 57: ......