2. Mounting 

2-1 Caution 

Danger

 

 

For prevention of electrical shock, power supply to the control panel should be 

disconnected before installation work. 

 

Caution

 

 

For installation, do not use any parts other than originally supplied ones.   

Failure to this may result in injury or breakdown of the cooling unit. 

 

Cut out the mounting surface of the enclosure as specified in the drawing of page 5. 
 

 

COOLCABI must be placed horizontally and   

perpendicularly within a tolerance of 

±

2

  in order 

to keep stable operation of the unit and 

to make a smooth drainage. 

 

Locate the unit so as to assure good ventilation and 

distance of at least 200mm from the walls or other 

units.   

Also,  there  should  be  no  hindrance  to  the  air 

circulation inside the control panel. 

Failure  to  the  above  may  result  in  poor  cooling 

performance or condensation. 

 
 

The supply voltage must be as specified on the rating 

plate of the unit. 

Electrical connection should be made via appropriate   

circuit breakers as shown in the right. 

Ground  the  wire  without  fail  to  prevent  electrical 

shocks 
Electrical works required for installation of the unit must be done only 

by specialists. 

Improper installation may result in electrical shocks or fires. 
For protection of the compressor, wait at least 30 minutes after installation before 

connecting power to start operation. 

 

Hermetically seal the control panel all round. 

Inferior sealing may cause condensation which lead to poor cooling efficiency. 
Put covers on the components inside the enclosure to protect them from cutting 

dust during installation work. 
[Short circuit] 

Electric  components  or  other  objects  near  the  cool 

air outlet may disturb cool air circulation. If the cool 

air  hit  against  them,  it  will  directly  return  to  the 

suction port without being distributed to the whole 

area in the enclosure. This causes not only troubles 

of  the  components  but  may  negatively  affect 

operation  of  the  cooling  unit  which  lead  to 

overcurrent and product failure. 

In  case  such  short  circuit  is  found  during  cooling 

operation,  improve  the  environment  by  attaching 

rectifying  plates  or  installing  agitation  fans  as 

necessary. 

 

COOL 

CABI 

Enclosure 

Earth 

R  S 

COOLCABI 

Rectifying 

plate 

 

Agitation 

fan 

 

Control 

equipment 

 

Cool 

air 

 

Содержание COOL CABI OCA-S2300AC

Страница 1: ...OCA S2300AC OCA S3000AC...

Страница 2: ...2 20 50 85 RH 70...

Страница 3: ...3 2 200mm 30 90 90 90 200 200...

Страница 4: ...4 P 5 OCA S2300AC A200 OCA S3000AC A200...

Страница 5: ...5 OCA S2300AC A200 OCA S3000AC A200...

Страница 6: ...6 50cm 50cm 50...

Страница 7: ...7 10 AWG24 12 0 2 2 5mm2 6 7 a 240V 1 5A 2 P 11 12 R S T E 1 2 3 AC200V IN...

Страница 8: ...8 OCA S2300AC A200 OCA S3000AC A200...

Страница 9: ...9 1 30mA 30 ON OFF 1 6 ON OFF ON OFF P 10 35 Set Up Down 35 30 45 Set Up Down 3 30 Set Down Up RUN ALARM Down Up Set...

Страница 10: ...t 3 Set Up Down Set 5 3 10 1 6 ON OFF 30 0 90 Up Down 3 45 35 51 2 1 20 0 0 99 0 1 99 1 100 1 99 9900 24 412 0 0 1 0 1 0 0 1 0 P 15 5 1 2 1 P 15 5 1 2 1 0 1 OPEN CLOSE OPEN CLOSE 0 1 0 0 0 3 0 1 2 3 P...

Страница 11: ...11 P 13 14 0 0 1 OPEN CLOSE 0 1 0 1 2 3 P11 12 1 0 3 0 1 2 3 7 7 60 3 3 3 10 ON OFF Set 3 30 Set 3 AS Ao 1 2 2 3 OPEN 0 8 AS 0 AS 1 AS 2 AS 3...

Страница 12: ...E1 E3 E4 E6 E7 OPEN 3 E3 E5 E6 E7 E8 SE CLOSE E1 E4 CLOSE E3 E5 E6 E7 E8 SE OPEN E1 E4 OPEN E4 P 10 0 Ao 1 AS 1 2 2 3 0 OPEN CLOSE CLOSE OPEN 1 OPEN CLOSE CLOSE OPEN 2 E5 E8 SE OPEN E1 E3 E4 E6 E7 OPE...

Страница 13: ...13 35 5 35 30 4 P 12 3 30 1 30 5 35 30 ON OFF ON OFF 35 30 ON OFF ON OFF...

Страница 14: ...14 7 3 5 5 35 30 ON OFF ON OFF 30 35 45 ON OFF ON OFF...

Страница 15: ...15 45 P 12 43 P 12 Set 3 P 12 Set 1 P 12 P 12 0 P 12 Set 3 OCA S2300AC A200...

Страница 16: ...16 P 12 OFF 1 1 OCA S2300AC OCA S3000AC...

Страница 17: ...17 OCA S2300AC A200 8 2 OCA S2300AC A200 8 3 2 1 OCA S2300AC A200 FM 2300ACIN FM 2300ACOUT OCA S3000AC A200 FM 3000ACIN FM 3000ACOUT 8...

Страница 18: ...18 50 45 P 9 P 3 OFF 7 5kW 1 4 P9 4 4...

Страница 19: ...4 7 14 5A 17 8 19 2A 2 1025 1220W 1405 1735W 1280 1530W 1825 2110W 650W 900W A 64dB HFC R407C 580g 780g 1770 W H D mm 650 447 400 760 447 400 48 0kg 57 0kg 3 20 50 85 RH 3 30 45 35 1a 240V 1 5A 2 COMM...

Страница 20: ...20 OCA S2300AC A200 OCA S3000AC A200 1 M8 4 M8 4 M8 4 M8 4 1 5m 2 1 1 1 1...

Страница 21: ...21 OCA S2300AC A200 OCA S3000AC A200 2 8 13 2 8 13 2 12 1 12 2 12 1 12...

Страница 22: ...22 1 13 64 19 10 4 431 1304 7000 21 TEL 053 522 5572 FAX 053 522 5573 7 2019 5...

Страница 23: ...1 Safety Precautions 2 2 Mounting 3 6 3 Wiring 7 9 4 Operation 9 14 5 Alarm Safeguard 15 16 6 Maintenance 16 18 7 Specifications 19 21 8 Warranty period 22 9 Waste disposal 22 Please read this brochu...

Страница 24: ...in short life or damage of the unit Shocks and vibrations should be strictly avoided at the site of use Never tamper or repair the main body Please consult with your local supplier for repairing servi...

Страница 25: ...out fail to prevent electrical shocks Electrical works required for installation of the unit must be done only by specialists Improper installation may result in electrical shocks or fires For protect...

Страница 26: ...d tighten the nut to securely fix the unit 6 To ensure keep the panel interior airtight caulk the gaps completely if any 7 Apply the enclosed Alarm explanation sheet to an appropriate place where read...

Страница 27: ...5 Cutouts View from outside the panel OCA S2300AC A200 OCA S3000AC A200...

Страница 28: ...closed L joint on the corner of the enclosure Let a drain hose go directly downward without kinks and windings Any part of a drain hose should not be higher than the level of a drain pipe of COOLCABI...

Страница 29: ...s no problem in supply voltage wiring connection and grounding 3 1 Wiring procedure Applicable wire range AWG24 to 12 0 2 to 2 5m 1 Strip the wire by 6 or 7 mm 2 Push down the Push button with a flath...

Страница 30: ...S T B C A Reverse phase prevention relay A C R S Y X Thermostat Float switch Sensor RY1 CN6 CN3 CN1 CN4 Fuse 250V 1A Control board 1 2 3 Terminal board CN8 E Overheat detector External fan x 4 FM2 FM2...

Страница 31: ...f injury Never operate COOLCABI leaving the control panel door open Failure to this may lead to excessive condensation and drainage volume as well as creating the possibility to allow condensate to en...

Страница 32: ...ting range 0 99 This is the function to remind you maintenance works in a timely manner 0 This function is ineffective 1 99 1 means 100 hours Notification period can be set between 100 to 9900 hours T...

Страница 33: ...eriod for restarting the compressor after shutdown For prevention of frequent ON OFF of the compressor cooling operation is suspended during the set period Display of software version This is to displ...

Страница 34: ...E7 E8 and SE OFF OPEN Alarm E1 and E4 OFF OPEN Alarm E4 is not output when Fo is set at 0 See page 10 Assignment table of Alarm output terminals Ao 1 AS Terminals 1 2 Terminals 2 3 Description Operati...

Страница 35: ...eration will not start for a certain period of time initial setting 3 min after cooling operation has stopped even if the internal temperature goes up to the set temperature 1 Continuous run Cooling o...

Страница 36: ...ts because the air is not circulated by the internal fan For protection of the refrigerant circuit the internal fan will not stop for 5 minutes after cooling operation has stopped The internal fan run...

Страница 37: ...mperature controller for more than 3 seconds to cancel the alarm The cooling unit will restart operation Caution Be sure to disconnect power and wait until the fans stop completely 3 E4 Maintenance re...

Страница 38: ...this failure turn off the power immediately and contact your supplier 9 tE Type Error Contact the supplier 5 2 Safeguard As a safeguard this product is designed to stop operation under an abnormal cur...

Страница 39: ...ord and then the cooling unit Pay attention not to pinch the cables 6 Put the front panel and the screw caps for eyebolt Please see the Page 18 for the model of replacement fan 6 3 Replacement of the...

Страница 40: ...r g Check temperature setting and the internal temperature In case of fan failure replace the fan h To check whether the fan works properly execute forcible cooling See 4 4 of page 9 If it did not run...

Страница 41: ...setting 35 Display Internal temperature Alarm code Operating lamp Alarm lamp Function Off temperature alarm Detection of abnormal heat dissipation Detection of temperature sensor disconnection Drainag...

Страница 42: ...ete set of supply Model OCA S2300AC OCA S3000AC COOLCABI 1 Fixing bolt M8 4 Washer M8 4 Spring washer M8 4 Nut M8 4 Drain hose 5m L joint 2 Terminal board 1 Packing 1 Alarm explanation sheet 1 Instruc...

Страница 43: ...de Cool air Warm air Air from outside Terminal board Operation panel External air inlet filter White For eyebolt 2 M8 Depth 13mm Side view Rear view Bottom view Top view For eyebolt Warm air Air from...

Страница 44: ...user Recovery of the refrigerant should be done by an authorized waste disposer Owner s management responsibility Check of equipment The enclosure cooling unit needs simple regular inspection Daily ch...

Отзывы: