ASSEMBLY 

 

 

 

IGNITION MODULE INSTALLATION

 

This product requires assembly.

 

  Ignition module must be installed inside the 

flame arrestor via a 1 ¼” diameter hole in the 
flame arrestor wall. Ignition module MUST be 
installed on a flat surface.

 

 

  Perform an initial inspection of the interior of the 

flame arrestor to confirm there is proper installation 
room inside the flame arrestor. 

 

  Ignition module is provided with two stainless steel 

washers and two rubber washers. Install washers 
according to Figure 2 (pg.II) to provide a water tight 
connection between flame arrestor and the ignition 
module.

 

 

 

CONTROL PANEL INSTALLATION

 

This product requires assembly.

 

  Install the control enclosure within reach of the 

cable provided with the unit (varying lengths 
available upon request).

 

  Control panel must be installed in the vertical position 

and leveled, allowing the battery to sit flat in the 
bottom of the enclosure when applicable. 

 

  Control panel includes mounting feet for easy 

installation on a flat surface. See Figure 3A & 3B (pg. 
III)

 

 

 
 

CABLE AND CLAM SHELL ASSEMBLY

 

WARNING - 

BEFORE BEGINNING THIS STEP 

CONFIRM THAT THE POWER SWITCH IS IN 
THE OFF POSITION. 

 

  Cable assembly between control panel and 

ignition module is a polarized cable.

 

  Line up keyway between connector and the 

receptacle, insert connector into receptacle, and 
carefully turn connector clockwise to thread 
connector. 

 

  Once the connection is made, install clam shell 

around the connectors (See Figure 4 pg IV). These 
shells are required to maintain Class 1 Division 2 
rating. Failure to apply clam shells could lead to a 
hazardous work environment. 

 

  Do NOT connect or disconnect cable assembly while 

power is on.

 

 
 
 

 
 

POWER CONNECTIONS 

The TotalArc system is shipped full factory wired 
except for the power system. See wiring instructions 
for all power options:

 

 

  Solar Power TotalArc (p/n 460246):

 

Solar Panel Wiring: 

WARNING – 

MAINTAIN SOLAR PANEL 

COVER UNTIL TOTALARC UNIT IS FULLY 
INSTALLED AND SOLAR PANEL  

 

         

IS TERMINATED IN ENCLOSURE 

1. Run solar panel SO Cord cable through cable 

gland on bottom of enclosure

 

2. Insert enough length of wire to reach the 

terminal blocks.

 

3. Tighten cable gland.

 

4. Terminate Solar Panel Wires:

 

 

Black Wire to Terminal Block 2

 

 

White Wire to Terminal Block 9

 

Battery Connection: 

1.  Install battery inside enclosure; Make sure it 

sits flat in bottom of enclosure. 

2.  Connect Red wire to Red battery terminal 

3.  Connect Black wire to Black battery 

terminal 

4.  Install battery terminal connectors 

according to Figure 5 (pg. IV) 

  120VAC Power TotalArc (p/n 460246):

 

Grid Power Wiring: 

**All field wiring and conduit to be sized 
by an electrical contractor**

 

 

 

 

1. Run conduit connection into plugged Myers Hub 

on bottom of enclosure panel                                 

***WARNING: PROPER HAZARDOUS 
LOCATION WIRING METHODS MUST BE USED 
WHEN INSTALLING AND TERMINATING THE 
TOTALARC RELIGHTER***

 

2. Insert enough length of wire to reach the terminal 

blocks.

 

3. Terminate wires to terminal blocks:

 

 

Black wire to Terminal Block L

 

 

White wire to Terminal Block N

 

 

Green wire to ground lug on back panel

 

 

Содержание TotalArc BMS 460246 SOLAR POWER

Страница 1: ...ct of Quality integrity and innovation from concept to commissioning That promise along with proper maintenance will ensure that your TotalArc Relighter gives you years of rugged trouble free performa...

Страница 2: ...or s manual Figure 1 1 ON OFF POWER SWITCH 2 STATUS INDICATOR LIGHT 3 IGNITION PUSH BUTTON 4 MAIN GAS SHUTOFF SOLENOID 5 TOTALARC ENCLOSURE 6 CUSTOMER POWER ENTRY 7 M12 RECEPTACLE 8 IGNITION MODULE CA...

Страница 3: ...II FIGURE 2 IGNITION MODULE Installation in Flame Arrestor For details see Installation instructions on page 7...

Страница 4: ...INSTALLATION TotalArc kit includes mounting feet for easy installation For details see Installation instructions on page 6 FIGURE 3B INSTALLATION MOUNTING PATTERN FOR TOTALARC ENCLOSURE SEE FIGURE 3B...

Страница 5: ...IV FIGURE 4 Clamshell Installation FIGURE 5 Battery Connection Detail SOLAR OPTION ONLY...

Страница 6: ...V FIGURE 6 Ignition Rod Installation Figure 7 BASO Pilot Safety Valve...

Страница 7: ...VI Figure 8 Solar Panel Assembly...

Страница 8: ...VII Figure 9 Solar Panel Assembly...

Страница 9: ...mportant Safety Instructions 2 Symbols 3 4 Electrical 4 Features 5 Assembly 5 7 Operation 8 9 Maintenance 10 Trouble Shooting 11 12 Wiring Diagrams 13 14 Warranty 15 Parts Ordering and Service Back Pa...

Страница 10: ...s system is provided with a solar panel and all required installation hardware The solar panel provided is sized to 35 Watts but solar systems can be supplied with a solar panel up to 50 Watts subject...

Страница 11: ...ntrol cable periodically and if damaged have it replaced by an authorized service facility Make sure all control cable clam shell guards are properly and securely attached prior to power up stage Use...

Страница 12: ...used on this product Please study them and learn their meaning Proper inter pretation of these symbols will allow you to operate the product better and safer SYMBOL NAME DESIGNATION EXPLANATION Safet...

Страница 13: ...t 25 C OGI PART 460312 VAC Powered Control Panel Nominal System Voltage 85 264 VAC Rated Current Input 1 35A at 120 VAC 0 65A at 230 VAC OGI PART 460371 VDC Powered Control Panel Nominal System Voltag...

Страница 14: ...ring shipping Carefully remove the product and any accessories from the box Make sure that all items listed in the packing list are included Donotdiscardthepackingmaterialuntilyouhavecarefully inspect...

Страница 15: ...all clam shell around the connectors See Figure 4 pg IV These shells are required to maintain Class 1 Division 2 rating Failure to apply clam shells could lead to a hazardous work environment Do NOT c...

Страница 16: ...tion is set tighten the set screw Ground connection remove one side of the metal clamp holding the ceramic insulator and install provided 12AWG THHN green ground wire with terminal connector and repla...

Страница 17: ...matic control pressure to flow to the remainder of the burner specific safeties If the pilot flame is lost and not relit the BASO will trip isolating and shutting down the burner pilot and venting off...

Страница 18: ...9 TYPICAL HEATER WITH TOTALARC RELIGHTER P ID ARRANGEMENT...

Страница 19: ...und connection at pilot assembly e Visually check the Control Panel and instrumentation for moisture condensation connections etc f In Northern locations where snow accumulation could be a problem cle...

Страница 20: ...h burner TCV RELEASED the system has maintained the main gas closed for a period of two minutes and has now been released TotalArc main gas valve released to OPEN BASO Pilot Guard should cool down and...

Страница 21: ...s power source can not be disconnected since it comes directly from solar panel Follow proper procedures while performing this test If no areas of concern are found please call OGI Service Department...

Страница 22: ...SCHEMATICS 13 SOLAR POWER TOTALARC P N 460246 120VAC POWER TOTALARC P N 460312 12 24VDC POWER TOTALARC P N 460371...

Страница 23: ...14 Enclosure Connections for all systems Trouble and Gas Shut Off Relay Connections for all systems TOTALARC TROUBLE RELAY DRY CONTACT SET CLOSED TROUBLE OPEN OKAY...

Страница 24: ...nufacturer s warranty and Seller must authorize return of such material prior to its return shipment Buyer shall bear the expense of packing and shipping proposed defective parts and components and th...

Отзывы: