31
Packet length - 40 bytes
Softcontrol Data/F package for external control:
byte
description
content
comment
0
0x75
Start identifier
1
0x30
Start identifier
2 - 3
STATUS
Status word (16 Bit)
siehe separate table
4
MASSEINHEIT
Unit of measurement
0 = °dH, 1 = °f,
2 = mmol/l, 3 = ppm
5
SPRACHE
Set language
0 = German, 1 = English
6 - 7
COUNTER
Measurment counter
is incremented after each
soft water measurement
8 - 11
RW
Raw water hardness (32 Bit)
Raw water hardness *100
12 - 15 WW
Soft water hardness (32 Bit)
Soft water hardness *100
16 - 19 GW_WW
Soft water limit value (32 Bit)
Soft water limit value *100
20 - 21 S_GUETE
Sensor quality (16 Bit)
Sensor quality*10
22 - 23 MESSPAUSE
Pause between measurements (16 Bit) Seconds
24 - 25 ALARMDELAY
Alarm delay (16Bit)
Seconds
26 - 29 Reserve
Currently not used
Assigned with 0
30 - 39 SENSORNUMMER
Sensor number
ASCII characters
The status word contains the coded representation of the current operating status of the device. If the
corresponding bit is set, the corresponding entry is active. The status word is coded as follows:
Bit
description
meaning
0
STATUS_WW
Soft water measurement is running
1
STATUS_RW
Raw water measurement is running
2
STATUS_MW
Mixed water measurement during
the sensor quality check
3
STATUS_CALIB
Sensor quality check is running
4
STATUS_ALARM_GW
Soft water limit value exceeded
5
STATUS_ALARM_SENSOR
no sensor detected or sensor quality too low
6
STATUS_OFFLINE
Device is offline
7
Reserve
currently not used
8 - 15
Reserve
currently not used
10.5.3.
Examples of data communication
Example SPS
Softcontrol Data/F (set hardness limit value)
byte
value
(decimal)
meaning
comment
0
117
Start identifier
1
48
Start identifier
2
2
SET_GW
Command for setting the
soft water limit value
3
0
Soft water limit value
25
LW = 0.25
4
0
Soft water limit value
5
0
Soft water limit value
6
25
Soft water limit value
7
0
currently not used