2.3 For connection with ducts or single duct:
-
Soft ducts must be avoided
-
Use rigid, smooth ducts (semi-rigid ducts are tolerated)
-
Observe the maximum permissible lengths L1 (≤ 10 M) and L2 (≤ 10 M).
The installation of accessory(ies) leads to an additional pressure loss: When calculating
the duct length, take into account the equivalent lengths of the installed accessories
(elbows, or other accessories...).
→
See Manual
for the equivalent duct lengths.
-
Wall grid:
it is strongly recommended to use the
Oertli
very low pressure loss grids.
Conncetion with ducts:
-
Remove the air inlet and air outlet grids (see illustration below).
-
For galvanised ducts: Insert
seals
(option HK437): Direct
lips downwards
.
Single-duct connection:
-
Only remove the
grid on the air outlet
side
(1)
-
For a galvanised duct: Insert a
seal
(option HK437): Direct
lips downwards
.
-
Leave the grid in place on the
air inlet
side: it prevents foreign objects from entering
and directs the air flow.