DAB Blue Diver Series Multistage Submersible pumps are designed for pumping DEF 
34% Urea solution (Diesel Exhaust Fluid) only. Never use these pumps for gasoline, 
kerosene, diesel fuel or any other distillates or solvents. 
 
ISO 22241 provides the Urea Diesel Exhaust Fluid (DEF) requirements including 1) 
quality of Urea DEF solution, 2) applicable test methods, 3) packaging transportation and 
storage requirements and 4) refilling interface requirements. 
 
Urea DEF solution must be handled and stored in compatible material, kept free of 
contamination, and stored at temperatures that will not cause the solution to deteriorate. 
The use of contaminated or out of specification Urea DEF can cause filter problems, 
clogged injectors, deterioration of the selective catalytic reduction process, or poison the 
vehicle

’s catalytic converter used in the exhaust system. Urea manufacturers may 

require a system inspection to insure that all components are Urea DEF compatible and 
that the tank and system have been properly cleaned, rinsed, and flushed before Urea 
DEF is delivered. 
 
The tank in which the pump is being installed must be vented in accordance with 
manufacturer’s installation instructions. Follow the tank manufacturer’s tank installation 
instructions. 
 
The use of NPT threaded piping and tank fittings for Urea DEF is not recommended. 
Threaded connections are likely to weep urea solution forming urea crystals at the point 
of the leak. However, if NPT threaded fittings are used, Urea DEF compatible thread 
sealant is necessary to achieve a tight connection. Use only pipe dope that is ISO 
22241-2 approved for DEF and suitable for stainless steel. Do not use PTFE-based pipe 
tape. Cleaning of all piping systems with deionized or distilled water per ISO 22241-3 is 
recommended prior to placing system into service. 
 
A product filter must be installed between the tank / piping and the dispensing point. The 
filter should be sized to insure that Urea DEF supplied to the dispenser nozzle meets the 
requirements of ISO 22241 and does not pass particulates that may clog the injector 
nozzles in the vehicle. 
 
The installation contractor should install the pump so that future service can be easily 
performed. Tank access ways, man ways, and pump mounting flanges should be large 
enough for the safe and easy removal of the pump for service and replacement. 

 
 
 
 
 
 
 
 
 

Содержание DAB BD-1000

Страница 1: ...0 Cedar Springs Road Spartanburg SC 29302 Tel 1 800 500 9311 Tel 864 573 9200 Fax 864 585 3635 www oecfh com INSTALLATION OPERATION SERVICE AND REPAIR MANUAL DAB BLUE DIVER SERIES SUBMERSIBLE DEF PUMP...

Страница 2: ...lue Diver Installation Diagram 7 7 3 Before Installation 8 7 4 Pump Discharge Piping for Blue Diver 1200 Only 9 8 0 Cleaning The Blue Diver Filter 9 9 0 Electrical Connection 10 9 1 Electrical Warning...

Страница 3: ...installed The entire operation must be carried out in a workmanlike manner Failure to comply with the safety regulations not only cause risk to personal safety and damage to the equipment but invalid...

Страница 4: ...ivery 2 25 GPM Liquid Temp Range 33 F to 90 F Max Immersion 33 Ft Storage Temp 33 F to 100 F Relative Humidity of Air MAX 99 Minimum Positive Head 6 Inches Max Starts Per Hour 30 Max Voltage Variation...

Страница 5: ...bility The Manufacturer does not vouch for correct operation of the pumps if they are tampered with or modified run outside the recommended work range or in contrast with the other instructions given...

Страница 6: ...nk in which the pump is being installed must be vented in accordance with manufacturer s installation instructions Follow the tank manufacturer s tank installation instructions The use of NPT threaded...

Страница 7: ...DEF Dispenser 4 Control Panel for Pump Protection 5 Level Control Sensor 6 Tank Fill 7 Pressure Vacuum Vent 8 Man Hole Cover Not Shown 9 Discharge Pipework 10 DEF Storage Tank Courtesy of Containment...

Страница 8: ...ctric cable The pump should not touch the tank bottom It should be suspended at least 3 inches from the tank bottom Minimum liquid level should be no less than 6 inches above the bottom of the pump Fa...

Страница 9: ...embly and check valve must be installed as shown in Fig 7 4 for the Blue Diver 1200 The bypass assembly ensures that when energized there will always be flow through the pump Blue Diver pumps rely on...

Страница 10: ...required for safe installations the above ground metal plumbing should be connected to the power supply as a ground as described in Article 250 80 of the National Electrical Code or Section 26 954 of...

Страница 11: ...s of less than 32 F the pump body must be completely emptied to prevent possible cracking of the hydraulic components This operation is advisable even in the event of prolonged inactivity at normal te...

Страница 12: ...s characteristics A Remove the obstructions as indicated in the chapter on Warnings Paragraph 6 4 B Change the impellers or remove the obstruction C Check good operation of the valve and replace it if...

Страница 13: ...warranted 18 months from date of installation or 24 months from date of manufacture Our Warranty will not apply to any product that in our sole judgment has been subject to negligence misapplication...

Страница 14: ...pg 14...

Отзывы: