Performance Specifications

Processor

28ADR/DDR/ADT/DDT, 48ADR/DDR/ADT/DDT

Control method

Stored program, cyclic operation

External Input/output

Base 28/48 points. 28 expansion points. 
Expandable to max. two expansion modules

Instructions

Basic

28 types

Advanced 139 

types

Processing
speed

Basic

Several 

µs per step

Advanced

Several to several tens of 

µs per step

Program capacity

9k words

Memory size

I/O (R)

R000.00 to R31.15 (512 points, 32 words)

Special internal 
contact (R)

R032.00 to R127.15 (1436 points, 96 words)

Link contact (L)

L000.00 to L063.15 (1024 points, 64 words)

Internal contact (M)

M000.00 to M127.15 (2048 points, 128 words)

Keep contact (K)

K000.00 to K127.15 (2048 points, 128 words)

Special contact (F)

F000.00 to F015.15 (256 points, 16 words)

Timer/Counter
(TC or TIM)

256 channels (Timer + Counter), 
Set value range: 0 to 65535

Timer: 0.01 second: TC000 to TC063 (64 channels)

0.1 second: TC064 to TC255 (192 channels)

Counter: TC000 to TC255 (256 channels)

Data register (W)

W0000 to W2047 (2048 words)

Special register (SR)

SR000 to SR511 (512 words)

Communications

Speed

9600, 19200, 38400, 4800 bps, automatically 
selected

Port

Port1: RS232/RS485, 9-pin female D-SUB

Port2: RS232/RS485, 8-pin modular terminal

Number of ports

2 ports

Supporting functions

2 of 4 step communications protocol (Port 1 and 2)

User-defined communications, Modbus slave 
(Port 2)

Special functions

High-speed counter

1 channel/32 bits built-in, single phase 8K, 
two-phase 4K

Pulse output

2 channels built-in (TR output model) 5 KHz

Input pulse catch

4 contacts built-in

Others

RTC

Built-in

PID

Supports 8 loop PID control

Programming
Tools

Programming S/W

Supports WinGPC 3.0 or higher for Windows

Memory backup

Battery backup, Backup using flash ROM

Содержание NX7 Series

Страница 1: ...re 8 Cables 8 Hardware Features 9 Specifications 10 General Specifications 10 Power Supply Specifications 10 Performance Specifications 11 Input Specifications 12 Output Specifications 13 Communication Specifications 15 Installing and Wiring 16 Product Dimensions 16 Installation Dimensions 16 Installation Space 17 Terminal Block Dimensions 17 Power Supply Wiring 18 ...

Страница 2: ...or liability for actual use based on the examples and diagrams No patent liability is assumed by OE Max Controls with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of OE Max Controls is prohibited Throughout this manual we use notes to make you aware of safety consider...

Страница 3: ...form a special operation during run such as program editing operation control or forced output make sure to perform it after ensuring safety Do not connect an external device or a hand held programmer HHP that uses internal power to the product when runnig Make sure to stop the system and ensure safety before connecting them Make sure to use an external device to PLC when configuring the protectiv...

Страница 4: ...25 in Input output and communication cables should be separated from power cables Give at least 200 mm space between them Otherwise generated noise may cause product malfunction We recommend installibng an insulation transistor near the front of the PLC Make sure to use twisted cables to prevent input noise For frame grounding perform class 3 grounding at 100Ω or less ground resistance or independ...

Страница 5: ...cause they melt deform or discolor PCB boards Precautions for use of power Run your PLC system only after the I O devices and motor devices have started For example first power on in the PROG mode then change the operation mode to RUN Make sure to power off I O devices after ensuring PLC operation is stopped If you power on off I O devices when the PLC system is in operation the system may malfunc...

Страница 6: ...put NX7 48DDR 28 point dc input 20 point relay output NX7 48DDT 28 point dc input 20 point transistor output Catalog number Input power I O specifications Remarks NX7 28EDR 24V dcb power supply 16 point dc input 12 point relay output 16 point 24V dc input 12 point relay output 2A per point NX7 28EDT 24V dc power supply 16 point dc input 12 point transistor output 16 point 24V dc input 12 point tra...

Страница 7: ...p connections etc 2 Off Disables termination for RS 485 communication On Enables termination for RS 485 communication COM1 RS232C RS485 9pin female D Sub 24V dc auxiliary output Panel fixing hole Battery mounting holder Input terminal Expansion unit connector Status LEDs LED Description RUN On when processor is in operation Flashes when processor is pausing PROG On when the program can be modified...

Страница 8: ... for 10 min Dust condition No conductive dust Chemicals No cutting oil and organic solvents Corrosive gas No corrosive gas Shock immunity 98m S2 or more 4 times X Y Z each direction Grounding Class 3 grounding 100Ω or less Case material PC ABS Cooling method Natural air cooling Ambience No corrosive gas no excessive dust Item AC input power DC input power Rated voltage 110 to 220V ac free voltage ...

Страница 9: ...er Counter TC or TIM 256 channels Timer Counter Set value range 0 to 65535 Timer 0 01 second TC000 to TC063 64 channels 0 1 second TC064 to TC255 192 channels Counter TC000 to TC255 256 channels Data register W W0000 to W2047 2048 words Special register SR SR000 to SR511 512 words Communications Speed 9600 19200 38400 4800 bps automatically selected Port Port1 RS232 RS485 9 pin female D SUB Port2 ...

Страница 10: ...range 10 8 to 26 4V Max input current 10 mA or less Min On voltage current 10 0V or more 3 0 mA or more Max Off voltage current 5V or less 0 6 mA or less Input impedance Approx 3 6 K Response time Off On 2 ms or less On Off 2 ms or less Internal current consumption 50 mA or less at 5V Polarity None Common method 8 points per common or 16 points per common Status display LED External connection met...

Страница 11: ...V dc Load voltage range 85 to 264V ac 10 to 30V dc Max load current 2A per point 6A per common for 6 points Response time Off On 10 ms or less On Off 10 ms or less Surge absorber Not applicable Internal current consumption 300 mA or less at 5V 500 mA or less at 5V Common method 1 4 and 6 points per common Status display LED External connection method Terminal block M3 0 terminal width 6 4 mm or le...

Страница 12: ... dc Polarity common Sink type NPN Max load current 0 4A per point 1 0A per common Max inrush current 3A 10 ms or less Off state leak current 100 A or less Respons e time Off On 1 ms or less On Off 1 ms or less Internal current consumption 5V 80 mA or less Common method 1 4 and 6 points per common Status display LED External connection method Terminal block M3 0 terminal width 6 4 mm or less Recomm...

Страница 13: ...lex asynchronous polling Data bit 8 bits Parity None Stop bit 1 bit Communication distance RS 232 15 m or less RS 485 1 2 Km or less Termination resistance COM1 adjusted by the internal DIP switch COM2 external user wiring 150 recommended Transmission cable Twisted pair cable Shielded cable COM1 comm port 9 pin female D Sub COM2 comm port 8 pin female RJ45 Status LED Flashes during communication C...

Страница 14: ...ase and expansion 48 points Installation Dimensions 28 points 48 points 100 mm 90 mm 79 0 mm 35 mm DIN rail mounting holder 76 6 mm 146 mm 90 mm 100 mm unit mm 146 0 mm 81 0 mm 31 9 in 9 5 3 0 87 0 mm 3 43 in 126 0 mm 4 96 in 87 0 mm 3 43 in 10 0 Φ 4 2 3 0 ...

Страница 15: ...tact defects leading to product damage or personal injury Make sure to disconnect power to the controller system before performing installation wiring maintenance and cleaning Never touch the power terminals when the power is on Otherwise it may cause electrical shock Route wires of different signal characteristics by separate paths Separate incoming power to the controller by a path separate from...

Страница 16: ...stance or Class D grounding to prevent voltage mixing between the frame ground and the power input terminals Ground the frame ground terminal with a dedicated Class 3 100Ω or less of ground resistance or Class D grounding Power source isolation transformer Noise filter If the secondary side of the isolation transformer and the noise filter is too far from the controller system and noise becomes ex...

Страница 17: ...NX7 Installation Instructions OE MAX Controls www oemax com Copyright 2004 OE MAX Controls ...

Отзывы: