Technical Data – 13
Chapter 3
TECHNICAL DATA
SPECIFICATIONS
The 5610 is a general purpose relay module with six Single Pole,
Double Throw (SPDT) relays and two Single Pole, Single Throw
(SPST) relays. The dry contacts are suitable for switching transduc-
ers, temperature sensors, low level signals, and low power levels.
Sockets connect the relays to the card, so replacing them is fast and
simple; no special tools are required. The 5610 does not have any
fuses. The contacts end with a terminal block. Isolation between
relays and the module circuitry is 500 volts.
The contacts are rated at 0.25 amps or 3 watts, whichever is higher.
Each relay channel is rated to 120 VAC; operation above 32 volts AC
or DC is not recommended for operator safety reasons.
Mapping
Occupies 16 I/O port addresses – port 100H as shipped. May be
remapped by jumper to any of 8 addresses on 16 byte boundaries.
Contact Rating
0.25A at 24 VDC, resistive.
Turn–on Time
<0.5 mS
Turn–off Time
<0.5 mS
Output Channels
Six SPDT redundant contact relay outputs and two SPST (Normally
Open) relay outputs.
Connectors
Screw terminals accept 12–22 AWG wire.
Содержание 5610
Страница 8: ...ii ...
Страница 12: ...Preface 4 This page intentionally left blank ...