982017-AIR-BASIC-Multitower-T201-EN01.docx

 

Page 31 of 60

 

Electrical connection 

 

 

CAUTION

 

Long-term  operation  of  a  three-phase  drive 
(compressor, pumps, fans) via a three-phase power 
supply with incorrect phasing will damage the drive. 

-

 

Ensure that all three-phase motors are 
connected to a three-phase supply with a 
clockwise rotating field.  

 

6.1  Cable cross-sections/ 

screened cable  

 
Cables should be selected by the electrician taking 
into  account  the  output  and  cable  lengths. 
Conventional  cables  with  multi-strand  cores 
should be used for wiring sensors and actuators. 
The following guidelines should be followed: 
 

Position  

min. cross-

section 

Connection  cables  220-240  VAC 

(pumps,  actuators)  Always  size 
connection  cables  according  to 
the local conditions. 

1.5 mm² 
 

Sensor  cables:

  (outdoor  sensor, 

etc.)  Always  route  sensor  cables 
away 

(min. 

20 

cm) 

from  

240 V/400 V cables.  
The  maximum  cable  length  must 
not exceed 50 m. 

1.0 mm² 
 

Bus  cables 

(eBus  e.g.:

 

room 

remote 

controls, 

auxiliary 

modules,  bus  connections  for 
cascades,  etc.)  must  always  be 
routed in a screened configuration. 
Only earth the screen once 

  on 

the heat pump to PE. 
 
OCHSNER 

recommends 

the 

following conventional cable: 
 

Y(ST)Y) 2x2x0.8 

 

CAUTION: 

OCHSNER  accepts  no  liability  for 
damage  caused  by  insufficient 
protection 

against 

electric 

emissions. 

0.8 mm² 
 

Table 4: 

Cable cross-sections 

 

6.2  PSU control contact 

 
In  the  case  of  tariff  switching  (with  interrupted 
power supply), the heat pump is temporarily shut 
down  by  the  PSU.  A  control  input  (jumper  on 
terminal  PSU,  terminal  strip)  is  provided  on  the 
controller  for  this.  Where  tariff  switching  takes 
place  inside  the  meter  (night  tariff),  the  PSU 
contact must not be made. In case of shutdown by 
the tariff contactor (sealed by the PSU, installed on 
site),  the  heat  pump  power  supply  is 
disconnected. The heat pump signal contact must 
be made via the tariff contactor auxiliary contact. 
 

High limit safety cut-out (HLSC) 

If an on-site high limit safety cut-out is installed, it 
can  be  connected  to  the  HLSC  contact  on  the 
terminal  strip.  This  shuts  down  the  feed  pump. 
This only applies for hydraulic connection versions 
7.1  and  7.2.  In  all  other  versions  the  HLSC  must 
interrupt the power supply of the on-site heating 
circuit pump 

directly

 
 

 
Observe  minimum  distances  between  sensor 
cables and 240 V/400 V. If this is not possible, use 
screened cables. Connect the screen to the  heat 
pump on PE. This is particularly important for the 
outdoor sensor wiring. 

All wiring/cables must be 

flexible (Ölflex)!

 

 

 

NOTE 

Содержание AIR BASIC 211 T201

Страница 1: ...982017 AIR BASIC Multitower T201 EN01 docx Page 1 of 60 Operating manual installation manual AIR BASIC 211 T201 AIR BASIC 618 T201 Air water heat pump Heating cooling DHW...

Страница 2: ...cal connection 24 4 1 7 T201 maintenance 25 5 Refrigerant lines 27 5 1 Outdoor unit connection 29 5 2 Indoor unit connections 30 5 3 Leakage test 30 6 Electrical connection 31 6 1 Cable cross sections...

Страница 3: ...appliance repairs modifications may only be carried out by authorised bodies Turn off all mains fuses of the system before carrying out any work on plug in strips or electrical connections wires Comm...

Страница 4: ...982017 AIR BASIC Multitower T201 EN01 docx Page 4 of 60 2 Appliance description 2 1 Available models BASIC 211 C11B T201 AIR BASIC 618 C12B T201...

Страница 5: ...tor C Temperature sensor air inlet evaporator OAT D Temperature sensor evaporator OMT E 4 way switching valve F Electronic expansion valve EEV G Temperature sensor compressor head CTT H Liquid separat...

Страница 6: ...982017 AIR BASIC Multitower T201 EN01 docx Page 6 of 60 3 2 Dimensions AIR BASIC 211 Figure 2 Outdoor unit dimensions AIR BASIC 211...

Страница 7: ...982017 AIR BASIC Multitower T201 EN01 docx Page 7 of 60 AIR BASIC 618 Figure 3 AIR BASIC 618 outdoor unit dimensions...

Страница 8: ...d installing the outdoor unit in an open and exposed location e g on a flat roof Wind can cause problems with de icing on the outdoor unit in defrosting mode due to increased heat dissipation We recom...

Страница 9: ...ppliance with access to refrigerant pipe connections and electrical connection of the outdoor unit to be installed The thicknesses of cover are average values and should be matched to local conditions...

Страница 10: ...s in mm The floor brackets must be anchored on site using long screws in the fully cured foundation strips tipping protection Recommendation Drill 2 holes in each of the floor brackets at the appropri...

Страница 11: ...e g 12x100 V2A with washer 2 Rubber support supplied with product 3 Foundation strips 4 Gravel 5 Topsoil 6 Non woven geotextile for cohesive soil 7 Drainage pipe 8 Frost penetration depth 1 Screw e g...

Страница 12: ...e g 12x100 V2A with washer 2 Rubber support supplied with product 3 Foundation strips 4 Gravel 5 Topsoil 6 Non woven geotextile for cohesive soil 7 Drainage pipe 8 Frost penetration depth 1 Screw e g...

Страница 13: ...30 M10 for sound insulation 3 5 1 Requirements for wall mounting Figure 10 Wall bracket dimensions L 600 mm H 340 mm Material S235JR RST 37 2 galvanised zinc coating min 50 m Load bearing capacity F1...

Страница 14: ...ll are derived from these Drill the holes in the wall Install the wall brackets Install the 4 rubber metal buffers for sound insulation to the wall brackets Observe the distances between holes for the...

Страница 15: ...he tundish should be installed away from electrical devices NOTE If secondary return circuits are used then an additional expansion vessel may be required Date table Minimum size of discharge pipe D1...

Страница 16: ...in hose Operating manual 1 expansion vessel incl fastening material 1 installation kit pressure reducing valve check valves expansion relief valve tundish Gaskets for the hydraulic connection heating...

Страница 17: ...ce and heat pump small Ensure that the floor has adequate load bearing capacity and is sufficiently level for weight see section Specification Data table The room must not be endangered by explosive d...

Страница 18: ...ith flat gasket e02 Heating return 1 union nut with flat gasket e50 Hot gas line e51 Liquid line c01 Cold water inlet 1 union nut with flat gasket c06 DHW outlet 1 union nut with flat gasket c10 DHW c...

Страница 19: ...ont cladding Remove the screw from the top centre of the appliance Unhook the front cladding towards the top Disconnect the control panel plug and the front panel earth wire Installing the front cladd...

Страница 20: ...tions 1 Pull the top section towards the front Figure 23 Separating the appliance sections 2 Tilt the top section towards the back Use the grip rail for better grip during transport Figure 24 Setting...

Страница 21: ...e 27 Assembling the appliance sections 2 Slide the top appliance section towards the rear until it is flush with the bottom section When the appliance sections are assembled correctly the end position...

Страница 22: ...ce must be operated with pressure fittings Cold water pipe Permitted materials are galvanised steel stainless steel copper and plastic CAUTION A safety valve is required DHW pipe Permitted materials a...

Страница 23: ...me fluxes used to solder pipes and fittings need to be flushed out with hot water Heat the cylinder to its normal operating temperature and flush all pipe work with hot water to ensure all flux and de...

Страница 24: ...ing circuit or several can be set up externally Connect the components of the mixed circuit to the following connections on the controller Mixer PIN 15 16 N PE Mixed circuit sensor PIN 43 GND Mixed ci...

Страница 25: ...ing valve MVH 41 42 Control elements eBus 43 Mixer sensor TMK 44 Outdoor temperature sensor TA 55 Default target value building management system BMS 4 1 7 T201 maintenance CAUTION Before any work is...

Страница 26: ...Clean the appliance via the inspection flange For tightening torques and flange bolts see Specification Sacrificial anode CAUTION If the wear indicator has changed from a white to red colour let a qu...

Страница 27: ...tractor When handling refrigerant wear appropriate gloves protective clothing and protective glasses Unit AIR BASIC 211 AIR BASIC 618 max length m 20 20 max height differential m 15 15 Refrigerant R41...

Страница 28: ...982017 AIR BASIC Multitower T201 EN01 docx Page 28 of 60 Figure 36 Refrigerant line routing D Pressure line suction line E Oil lift bend min bending radius 5x diameter max 15 m max 15 m...

Страница 29: ...tem Figure 37 View of solder crimp fitting The solder crimp fittings provide a better seal than crimps made on site Leak rate 1 g year CAUTION OCHSNER customer service will solder the crimp fittings p...

Страница 30: ...s are located on the top of the indoor unit Customer service will solder them in this location during commissioning Do not bend these pipes Bend the pipes coming from the outdoor unit for connection S...

Страница 31: ...ing conventional cable Y ST Y 2x2x0 8 CAUTION OCHSNER accepts no liability for damage caused by insufficient protection against electric emissions 0 8 mm Table 4 Cable cross sections 6 2 PSU control c...

Страница 32: ...PE 2 PSU cable remove the factory fitted jumper 3 Control cable 240 V 4 Supply of integral 8 8 kW E rod 5 Bus connection between indoor and outdoor units lay the screen on both sides 6 Outdoor sensor...

Страница 33: ...unit C Meter distributor 1 Outdoor unit supply 1x 220 240 VAC 50 Hz N PE 2 PSU cable remove the factory fitted jumper 3 Control cable 240 V 4 Supply of integral 8 8 kW E rod 5 Bus connection between...

Страница 34: ...PSU cable remove the factory fitted jumper 3 Control cable 240 V 4 Supply of integral 8 8 kW E rod 5 Bus connection between indoor and outdoor units lay the screen on both sides 6 Outdoor sensor 7 Ver...

Страница 35: ...nstall the system according to the relevant standards and local guidelines KEY Low voltage cables must be routed away from 240 V 400 V cables a Heat pump terminal strip 1 Wiring charging pump buffer l...

Страница 36: ...fer sensor TPM NOTE In systems with direct heating circuit install the TPO sensor in the heating flow of the heat pump indoor unit Install the TPO sensor in the indoor unit at the marked location on t...

Страница 37: ...Check whether the outside temperature sensor is correctly placed and connected Check whether the power supply is connected correctly Check whether the signal cable to the heat pump bus cable is corre...

Страница 38: ...ion pump Heat pump is running heating output too low Excessive heat demand Reduce heat load Source system overstretched Reduce heat load Heat pump is switched to boiler priority Check controller setti...

Страница 39: ...source system WQA using the flow meters specified by OCHSNER We recommend that when non routine work takes place requiring refilling e g system alteration or pipe breakage a current water assessment b...

Страница 40: ...d service not only helps to save energy but also protects the environment In addition correct care of the heating system is necessary to ensure many years of service life and indeed to extend the serv...

Страница 41: ...e decommissioned by an authorised specialist contractor refrigeration air conditioning heating The refrigerant or brine should be drained removed and properly recycled or disposed of by the contractor...

Страница 42: ...pressure Design Pressure upper indirect coil MPa 0 3 Max permissible temperature C 89 Electrical details Rated control voltage V 230 Control phases 1 N PE Control circuit fuse A 1xB16 Rated voltage em...

Страница 43: ...pressure bar 3 Test pressure bar 4 5 Max permissible temperature C 95 Water hardness dH 3 pH value with aluminium compounds 8 0 8 5 pH value without aluminium compounds 8 0 10 0 Conductivity softenin...

Страница 44: ...r T201 EN01 docx Page 44 of 60 11 2 Performance figures 11 2 1 AIR BASIC 211 Figure 45 Performance curveAIR BASIC 211 X air temperature C Y heating output kW X air temperature C Y power consumption kW...

Страница 45: ...45 of 60 11 2 2 AIR BASIC 618 Figure 46 Performance curve AIR BASIC 618 X air temperature C Y heating output kW X air temperature C Y power consumption kW X air temperature C Y COP max output max outp...

Страница 46: ...es W 79 indoor outdoor Sound power level dBA 62 Controller class with room remote control VI Controller contribution 4 Controller class without room remote control II Controller contribution 2 AIR BAS...

Страница 47: ...portion 2 2 00 3 5 00 4 1 00 5 6 00 6 0 50 7 5 00 8 0 50 9 1 50 10 0 50 11 3 50 12 0 50 13 3 00 14 0 50 15 0 50 16 0 50 17 2 00 18 0 50 19 1 50 20 0 50 21 0 50 22 0 50 23 1 50 25 1 50 25 0 50 Table 7...

Страница 48: ...of 50 C The maximum flow temperature TWV of the heat pumps is 55 C at 15 C outdoor temperature Therefore a max system temperature of 50 C is recommended when designing the system Limits of use for ou...

Страница 49: ...indoor unit hydraulic residual head Figure 48 T201 indoor unit heating circuit residual head 11 7 Recommended flow rates AIR BASIC 211 C11B T201 1 4 m h AIR BASIC 618 C12B T201 1 9 m h T201 indoor un...

Страница 50: ...982017 AIR BASIC Multitower T201 EN01 docx Page 50 of 60 11 8 Declaration of conformity...

Страница 51: ...982017 AIR BASIC Multitower T201 EN01 docx Page 51 of 60...

Страница 52: ...982017 AIR BASIC Multitower T201 EN01 docx Page 52 of 60...

Страница 53: ...982017 AIR BASIC Multitower T201 EN01 docx Page 53 of 60...

Страница 54: ...982017 AIR BASIC Multitower T201 EN01 docx Page 54 of 60 11 9 ERP Data...

Страница 55: ...982017 AIR BASIC Multitower T201 EN01 docx Page 55 of 60...

Страница 56: ...section 20 Figure 25 Assembling the appliance sections 1 21 Figure 26 Positioning aid 21 Figure 27 Assembling the appliance sections 2 21 Figure 28 Drain hose safety valve 22 Figure 29 Filling the hea...

Страница 57: ...982017 AIR BASIC Multitower T201 EN01 docx Page 57 of 60...

Страница 58: ...982017 AIR BASIC Multitower T201 EN01 docx Page 58 of 60...

Страница 59: ...982017 AIR BASIC Multitower T201 EN01 docx Page 59 of 60...

Страница 60: ...CHSNER W rmepumpen GmbH Germany D 60314 Frankfurt a M Riederhofstra e 27 Hotline for system partners 49 0 1805 832840 Customer service hotline 49 0 69 256694 495 kontakt ochsner de www ochsner com OCH...

Отзывы: