![OCEANAIRE PWC60 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/oceanaire/pwc60/pwc60_engineering-installation-and-service-manual_3240479007.webp)
SERVICE CORD
All POLARIS Series units are equipped with the standard ten foot long service cord with
plug configurations and receptacle requirements as shown in this chart. PWC1011,
PWC1211, PWC1811, PWC2412 and PWC3612 units come with
LCDI
(Leakage Current
Detection & Interruption) devices that serve as a means of electrical protection.
CAUTION—DO NOT USE THE LCDI AS AN ON/OFF SWITCH FOR THE UNIT
All 3-phase models are equipped with locking plugs for added connection reliability. Re-
fer to the chart below for plug and receptacle details for all POLARIS models.
A DAMAGED LCDI POWER SUPPLY CORD MUST BE REPLACED
WITH A NEW POWER SUPPLY CORD OBTAINED FROM
OCEANAIRE, AND NOT REPAIRED
5
UNIT/MODEL
PLUG CONFIGURATION
RECEPTACLE
115 VOLT
PWC1211
PWC1811
NEMA-5-15R
208-230 VOLT SINGLE PHASE
PWC2412
PWC3612
NEMA 6-20R
208-230 VOLT SINGLE PHASE
PWC6012
NEMA 6-50R
208-230 VOLT 3-PHASE
PWC3632
NEMA L15-20R
208-230 VOLT 3-PHASE
PWC6032
NEMA L15-30R
460 VOLT 3-PHASE
PWC3634
PWC6034
NEMA L16-20R
15A-125 VOLT
NEMA 5-15P
20A-250 VOLT
NEMA 6-20P
30A-250 VOLT
NEMA 6-30P
20A-250 VOLT
NEMA L15-20P
30A-250 VOLT
NEMA L15-30P
20A-460 VOLT
NEMA L16-20P