WARNINGS (for using R290/R32 refrigerant only)

Ensure that seals or sealing materials have not degraded such that they no longer serve the 

purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in 

accordance with the manufacturer's specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection 

equipment. Intrinsically safe components do not have to be isolated prior to working on them.

8. Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that 

this will not exceed the permissible voltage and current permitted for the equipment in use. 

Intrinsically safe components are the only types that can be worked on while live in the 

presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace 

components only with parts specified by the manufacturer. Other parts may result in the ignition 

of refrigerant in the atmosphere from a leak.

9. Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp 

edges, or any other adverse environmental effects. The check shall also take into account the 

effects of aging or continual vibration from sources such as compressors or fans.

10. Detection of flammable refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or 

detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall 

not be used.

11. Leak detection methods

The following leak detection methods are deemed acceptable for systems containing flammable 

refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the 

sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be 

calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition 

and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage 

of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the 

appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable 

for use with most refrigerants but the use of detergents containing chlorine shall be avoided as 

the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is 

suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found 

which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by 

means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen

(OFN) shall then be purged through the system both before and during the brazing process.

12. Removal and evacuation

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional 

procedures shall be used. However, it is important that best practice is followed since 

flammability is a consideration. Opening of the refrigeration systems shall not be done by 

brazing. The following procedure shall be adhered to:

Remove refrigerant;

Purge the circuit with inert gas;

Evacuate;

Purge again with inert gas;

Содержание OBZ-06CR3

Страница 1: ...Read this owner s manual thoroughly before operating the appliance and keep it handy for reference at all times OBZ 06CR3...

Страница 2: ...aintenance or have problems installing the unit If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Inside...

Страница 3: ...nts It may cause an electric shock Do not allow water to come into contact with any electric parts It may cause failure or electric shock Do not use a power outlet or a power cord if it s loose or dam...

Страница 4: ...may enter the unit and degrade the insulation which could lead to electric shock Do not put a pet or house plant where it will be exposed to direct air flow This could injure the pet or harm the plan...

Страница 5: ...ve chosen This information can be found on the serial plate which is located on the side of the cabinet and behind the grille If the air conditioner is to be installed in a window you will probably wa...

Страница 6: ...ed assessment authority which authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification NOTE Do not use this device to turn the unit...

Страница 7: ...rant R32 is used in air conditioner Please follow the instruction carefully to avoid any hazard IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit...

Страница 8: ...ried out Work in confined spaces shall be avoided The area around the workspace shall be sectioned off Ensure that the conditions within the area have been made safe by control of flammable material 4...

Страница 9: ...t to being corroded or are suitably protected against being so corroded 9 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component...

Страница 10: ...ked flame shall not be used 11 Leak detection methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used t...

Страница 11: ...e shall be taken not to overfill the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to com...

Страница 12: ...ted shut off valves in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working order with a set of instr...

Страница 13: ...NOTE The following instructions represent the control panel on the unit the same instructions can be used for the remote control ADJUSTS TEMPERATURE OR TIME ACTIVATES TIMER CHECK FILTER RESET BUTTON...

Страница 14: ...mode On DRY mode the fan speed is set to LOW automatically To select mode press the Mode button Each time you press the button the mode will change based on the sequence from AUTO COOL DRY and FAN The...

Страница 15: ...selected temperature This ends the Sleep mode and the unit will continue to operate as originally programmed The Sleep mode program can be cancelled at any time during operation by pressing the SLEEP...

Страница 16: ...Filter for more efficient operation The LED light will illuminate after 250 hours of operation To reset after cleaning the filter press the Check Filter button and the light will go off Press or hold...

Страница 17: ...c 3 minute time delayed start if the unit is turned off and on too abruptly This prevents overheating of the compressor and possible circuit breaker tripping The fan will continue to run during this t...

Страница 18: ...these instructions with the Consumer Note to Consumer Keep these instructions for future reference Skill level Installation of this appliance requires basic mechanical skills Completion time Approxima...

Страница 19: ...place it the top rail of the unit...

Страница 20: ...n a floor a bench or a table Be sure that the left and right window filter panels are on the proper side When installed the flange for securing the panel in place to the window sill should be facing i...

Страница 21: ...unit see Fig 13 Keep a firm grip on the air conditioner carefully place the unit into the window opening so the bottom of the air conditioner frame is against the window sill Fig 5 Carefully close the...

Страница 22: ...ccumulated Rain Water or Condensation must be allowed to drain out Turn the AC off and disconnect the power cord Remove sash seal from between windows and unscrew safety lock Remove screws installed t...

Страница 23: ...er use hot water over 40 C 104 F to clean the air filter Never attempt to operate the unit without the air filter Be sure to unplug the air conditioner to prevent shock or fire hazard The cabinet and...

Страница 24: ...ilter as instructed on the CLEANING AND MAINTENANCE SECTION of this manual The temperature may be set too high Set the temperature control to a lower setting Air directional louvers may be positioned...

Страница 25: ...low water to drain out Refer to the HOW TO INSTALL section on page 19 or check with the person who installed the unit initially The noise may be due to window vibration This can happen when the air co...

Страница 26: ...sound of rushing air being moved by the fan High Pitched Sound High efficiency compressors may have a high pitched sound during the cooling cycle Vibration The unit may vibrate and make noise because...

Страница 27: ......

Страница 28: ......

Отзывы: