TO CHECK THE NUMBER OF HOURS ON THE UNIT
1) Disconnect unit power, and reconnect unit power.
2) When
“888”
appears in display, push and release the arrow down button
3) The first set of numbers displayed reads thousands of hours:
02 = 2000, 04 = 4000 hours, 00 means less than 1000 hours.
4) The second set of numbers read hours directly:
58 = 58 hours. 742 = 742 hours.
6) Add the 2 number sets together to get total hours.
03 and 486 = 3486 hours. 01 and 59 = 1059 hours.
TOTAL HOURS REPRESENTS COMPRESSOR
“
RUN
”
TIME
MODEL
CODE SETTINGS
2OACH12
P1 = 65, P2 = 45
2OACH18
P1 = 80, P2 = 50
2OACH24
P1 = 70, P2 = 50
2OACH36
P1 = 85, P2 = 40
2OACH60
P1 = 85, P2 = 45
2OACH PROGRAM SETTINGS
NOTICE
Program Parameters are NOT controller default values.
They are OceanAire Factory Settings
DISPLAY FAULTS
LAC
………
Low AC line power
AAA
………
Failed Air Sensor (unit will not run)
CON
………
Empty Condensate Bucket—Units with a bucket
Condensate Pump Over
-
Flow Alarm—Units with pump
High Pressure Cut
-
Out—Restricted Air Flow
correct problem, and re
-
set unit at HP RESET
19
Содержание 2OACH SERIES
Страница 26: ...24 PIPING SCHEMATIC ...
Страница 27: ...25 WIRING SCHEMATIC FOR 2OACH12 18 and 24 DISCHARGE TEMP SENSOR ...
Страница 28: ...26 WIRING SCHEMATIC FOR 2OACH3612 DISCHARGE TEMP SENSOR ...
Страница 29: ...27 WIRING SCHEMATIC FOR 2OACH6012 DISCHARGE TEMP SENSOR ...
Страница 31: ...29 WIRING SCHEMATIC FOR 2OACH3632 DISCHARGE TEMP SENSOR ...
Страница 32: ...30 WIRING SCHEMATIC FOR 2OACH3634 DISCHARGE TEMP SENSOR ...
Страница 33: ...31 WIRING SCHEMATIC FOR 2OACH6032 DISCHARGE TEMP SENSOR ...
Страница 34: ...32 WIRING SCHEMATIC FOR 2OACH6034 DISCHARGE TEMP SENSOR ...