Mode setting options (see above for value details)
64
40065
UINT16
input 1 mode (NV/r/w)
65
40066
UINT16
input 2 mode (NV/r/w)
66
40067
UINT16
input 3 mode (NV/r/w)
67
40068
UINT16
input 4 mode (NV/r/w)
68
40069
UINT16
input 5 mode (NV/r/w)
69
40070
UINT16
input 6 mode (NV/r/w)
70
40071
UINT16
input 7 mode (NV/r/w)
71
40072
UINT16
input 8 mode (NV/r/w)
73
40074
UINT16
input broken wire alarm bitmap. (resistance, current modes only) Resistive mode: bit
set when resistance is off-scale-high. 4-20mA mode: bit is set when current is below
4mA.
74
40075
UINT16
relay output 1 (r/w) 0=open, 1=closed, defaults to open on power-up. r/w allowed when
register 41030 = 0.
75
40076
UINT16
relay output 2 (r/w) 0=open, 1=closed
System settings and information
1002
41003
UINT16
serial number bytes 1,2
1003
41004
UINT16
serial number bytes 3,4
1004
41005
UINT16
serial number bytes 5,6
1005
41006
UINT16
firmware version (major)
1006
41007
UINT16
firmware version (minor)
1011
41012
UINT32
uptime MSW number of seconds since IO module booted.
1012
41013
UINT32
uptime LSW
1013
41014
UINT16
hardware version (major) for example: 8332
1014
41015
UINT16
hardware version (minor) MSB = pcb rev, LSB = part rev. value 1=Rev_A, 2=Rev_B,
etc.
1015
41016
UINT32
hardware Date of Manufacture (MSW)
1016
41017
UINT32
hardware Date of Manufacture (LSW) time, UTC, unix epoch, seconds past 1970.
1017
41018
UINT16
RS485 Stats: Good RX (all packets received)
1018
41019
UINT16
RS485 Stats: Total TX
1019
41020
UINT16
RS485 Stats: TX failed
1020
41021
UINT16
clear min/max/ave (r/w) read returns 0, write any value to clear min/max/ave for all
channels.
1024
41025
UINT8
reason for reboot. 0x01=POR, 0x02=EXTR 0x04=WDTR
0x08=BODR,0x8000=WDTOF
1025
41026
UINT16
power supply voltage monitor. scale: x100, volts
1026
41027
INT16
pcb temperature monitor. scale: x100, degrees F.
1027
41028
UINT16
5V internal power supply voltage monitor. scale: x100, volts
1028
41029
UINT16
RS485 baud rate. 2=9600, 3=19200.
Modbus function 0x11 Slave ID response will report the following:
"Obvius, A8332-8F2D, IO Module, 8-Flex, 2-DO", id=48