AcquiSuite Administration Overview

The AcquiSuite should now be available on the local area network for you to access using a web browser such as Internet 
Explorer or Netscape.

Step 1

 - Use your web browser to connect to the AcquiSuite by entering

http://192.168.40.50/setup/
Where 192.168.40.50 is the IP address displayed on the on the AcquiSuite LCD display.

Step 2

 - When prompted, use the following default login information

Login: admin
Password: admin

Step 3

 - Your web browser should now display the AcquiSuite configuration menu. To the left, a list of configuration 

options are available. On the right, a specific configuration page will be shown. The first page is a welcome message with 
some system status information. Proceed with the configuration of the AcquiSuite using your web browser.

Step 4 -

 Click on the 

+

 mark next to the Accounts menu. Select the Admin account, and click 'Change Password'. All units 

are shipped with the same factory default password, and it should be changed to prevent unwanted access.

Step 5 -

 Expand the Networking option, and select setup. Verify the addresses are consistent with those in the "Network 

Address Worksheet."

Step 6 -

 Expand the Modbus option, and select "Device List." You should see a list of each Modbus device attached to the 

AcquiSuite. Before the AcquiSuite can begin logging data, each Modbus device must be assigned a unique name.

A. Click the device number to the left of the unconfigured Modbus device. 
B. A page with the current device status and readings will be displayed. Click on the 'configure' button at the bottom of 

the page. 

C. Enter a name for the device in the supplied field. 
D. Change any low and high range alarm settings you may need.  (optional)
E. Click the 'Save' button at the bottom of the page to save your changes. 
F. Repeat these steps for each Modbus device. 

Some devices may require additional information. For example, the Veris H8238 Multi circuit power meter allows the CT 
size to be specified. The Obvius A8923-4 IO Module and the A8812 AcquiSuite internal IO module have additional 
configuration options on each data point line to specify the details of the analog or pulse input. These include the 4-20mA 
device scale, multipliers and engineering units. Each 4-20mA or 0-10Vsensor should be supplied with technical information 
including the low and high range values  that can be used to configure the AcquiSuite. Also, the AcquiSuite has many 
common sensor types pre-programmed that can be selected from a drop down list.  Review the Modbus Advanced 
Configuration Options section of this manual for further configuration details. 

Step 7 -

 Select the Modbus/Setup menu option. Specify the Modbus Loop Name.  This will become the name of the 

AcquiSuite. This is the name that will appear on the BMO website service (if subscribed). Specify the data logging period. 
The default is 15 minutes.

Step 8 –

 Decide upon a method of data transfer.  (see section later in this document) . If you select the HTTP/Post method to 

send data to the BMO website, you can configure this by selecting the “LogFileData, Setup/Upload” page.

A. Make note of the AcquiSuite serial number. 
B. Select upload options as needed for time of day to upload the data and retry control. 
C. Check the checkbox to allow remote configuration.  This will allow you to reconfigure the AcquiSuite from the 

BMO web site without having to connect directly to the AcquiSuite. 

D. Specify the "Target address to upload data." This is the website address where the AcquiSuite will send the 

collected data. If you have an in-house data collection service, you should enter the address of your data server in 
this field. Obvius also provides a service called Building Manager Online that can collect and report data for you. If 
you are using the BMO service, the target address to upload data should be set to 
http://www.buildingmanageronline.com/upload.php 

E. When configuring the AcquiSuite to send data to the BMO site or your own data collection server, the AcquiSuite 

will authenticate itself with the server by using the serial number and a password. This password must be supplied 
here, and can be obtained when you subscribe for the BMO service, or by your database administrator. 

F. Click "Apply" to save your changes. 

If you select a manual transfer method, remove (blank out) the target address in the Modbus/Upload Data page.

Page 13

A8812 AcquiSuite – Data Acquisition Server

Shop for Power Metering products online at:

1.800.561.8187

www.

PowerMeterStore

.ca

Содержание A8812

Страница 1: ...uisition Server Obvius LLC Installation and Operation Manual Model A8812 Date Aug 16 2011 Page 1 A8812 AcquiSuite Data Acquisition Server Shop for Power Metering products online at 1 800 561 8187 www...

Страница 2: ...intended for use in critical applications such as nuclear facilities human implantable devices or life support Obvius is not liable in whole or in part for any claims or damages arising from such use...

Страница 3: ...lout to an ISP or RAS 25 GSM GPRS Cellular modem A8812 GSM only 25 Modem PPP Dialin 26 Dialin from a computer to the AcquiSuite 26 Example Dialin from a WinXP computer 27 System Options 28 Status 28 P...

Страница 4: ...rator Gateway address check with system administrator DNS server address check with system administrator HTTP Proxy address optional may be required if the AcquiSuite is behind a firewall check with s...

Страница 5: ...to consult the operating instructions provided with the product This symbol indicates the presence of electric shock hazards This symbol indicates Do not apply to or remove from hazardous live conduct...

Страница 6: ...0 c 1k 10k 1 of 10k at 20 c 10k 47 5k 1 of 47 5k at 20 c 47 5k 100k 1 of 100k at 20 c 100k 10M accuracy unrated Pulse mode intended for use with dry contact outputs consumption rate runtime status Sta...

Страница 7: ...l materials from shipping box and verify all required components are available Step 2 Mount the AcquiSuite on the wall or other appropriate location Page 7 A8812 AcquiSuite Data Acquisition Server Sho...

Страница 8: ...Modbus FAQ Low Voltage analog pulse and RS485 wiring that enters electrical panels must have a minimum insulation rating that exceeds the voltage inside the panel In addition other regulations may app...

Страница 9: ...or status mode the LED is on when contacts are closed In analog 4 20mA and 0 10V mode the led blinks quickly 2hz to indicate an over range alarm error In 4 20mA mode when the input current is less th...

Страница 10: ...omputer such as a laptop primary connection will be dialin or dialout by modem You will need the following information from your network administrator The addresses will be in the form of where refers...

Страница 11: ...ct to allow the AcquiSuite to reboot Once the AcquiSuite has rebooted the new IP address will be displayed on the console If DHCP addressing was specified the server assigned address will be displayed...

Страница 12: ...utton B In the network setup dialog there should be a list of items including adapters clients and protocols Locate the item labeled Internet Protocol TCP IP Note If you have multiple ethernet cards y...

Страница 13: ...g or pulse input These include the 4 20mA device scale multipliers and engineering units Each 4 20mA or 0 10Vsensor should be supplied with technical information including the low and high range value...

Страница 14: ...each Modbus Modbus Device List The AcquiSuite automatically searches for Modbus devices on the RS485 serial loop The Modbus Device List page will show a listing of all the currently detected or confi...

Страница 15: ...l number and firmware version when available for all devices in the Modbus device list Show stats show packet counters for all devices in the device list These include Sent Total number of packets sen...

Страница 16: ...AcquiSuite will log data for it Low Alarm High Alarm Specify a threshold for the alarm If the data point is recorded below the Low Alarm or above the High Alarm levels at the time a log entry is take...

Страница 17: ...fault TCP port is 502 on most gateways For local Modbus devices attached to the AcquiSuite RS485 port use 502 Device Name You must provide a name for the Modbus device to identify it in the device lis...

Страница 18: ...level fields will allow editing Type in a name for the device in the space provided at the top of the page The name should describe the purpose or location of the IO module For device 250 you may wan...

Страница 19: ...ck the console check box for any data points that should be displayed on the LCD console 6 Click the Advanced button in the lower right corner of the page For the A8812 onboard IO there are several op...

Страница 20: ...t of the hour For example if the log period is 15 minutes log readings will be taken at 0 15 30 and 45 minutes past the hour The log period is not calculated based on 15 minutes after the last reading...

Страница 21: ...result of that query Full Debug Complete listing of all queries including hex dumps of all data sent received Search for Modbus RS485 Devices This option allows the AcquiSuite to search for Modbus de...

Страница 22: ...quiSuite Data is received and uniquely identified by the sensor s serial number Each sensor may be given a name and some have additional options to configure such as input value scaling ModHopper Map...

Страница 23: ...NS server provided by your dialup isp If you only use the AcquiSuite on a crossover cable and or dialin mode you should leave these blank DHCP enable disable If you LAN has a DHCP server you may enabl...

Страница 24: ...l allow the system debug log to show a complete report of the PPP connection status This will include the PPP session negotiation for an IP address and other connection parameters You must click the s...

Страница 25: ...firm a modem answers the phone If so hangup attach the AcquiSuite to the phone line and proceed to the next step Step 3 Select the Network PPP0 ModemSetup option from the AcquiSuite configuration webp...

Страница 26: ...m any generic PPP system including MacOS Linux Windows 9x XP and 2000 The dialin feature is disabled by default and must be enabled from LCD console or the dialin options menu in order to receive call...

Страница 27: ...cted preceded by windows hanging up promptly after connecting to the AcquiSuite If that is the case a slight delay in the dial process for windows will correct the problem Adding this delay in a dial...

Страница 28: ...ons Date time in UTC and Local time Date time dropdown menus to select the current Local time manually Timezone a drop down list of the supported timezones Time sync protocol Select NTP or Rdate Most...

Страница 29: ...all the returned timestamps to local time before drawing the graph This is useful if you do not have detailed control over the graph legend drawing process This technique will not properly graph acros...

Страница 30: ...o do some basic network tests These are as follows Ping send an echo request to the specified host Traceroute Send an echo request to the target address and attempt to locate every router in between t...

Страница 31: ...s shown on the console the menu button will change the menu option and the select button will take action on the currently displayed option Some options provide sub menus others allow you to edit the...

Страница 32: ...ex io inputs This module shows up in the modbus listing as device 250 and is counted in the number of devices OK or New Ie if you have 1 AcquiSuite A8812 with a single modbus power meter the device co...

Страница 33: ...range alarm for data point 2 The third column shows point 1 as invalid and the fourth line shows the Modbus device is not responding Notice the following columns are shown 1 Date Time in UTC GMT time...

Страница 34: ...the configuration file 193 Modbus device s serial number changed could be two devices with the same Modbus address Low High Range Alarms This number is a hex representation showing which data points...

Страница 35: ...important to have a descriptive name in this field Step 2 Select the Log File Data Setup Upload menu option The following features are available AcquiSuite Serial Number This is the serial number that...

Страница 36: ...quiSuite uploads data to a database webserver push HTTP Direct from the AcquiSuite The AcquiSuite has the ability to export log file data to a web browser directly from the setup web pages To use this...

Страница 37: ...DL to delete log files from the flash memory With EnertraxDL simply check the setup checkbox to delete log data after download For FTP the process is essentially the same process as the manual FTP da...

Страница 38: ...on of custom web pages Further examples of XML and its uses are available on the Obvius website in the Documentation Technotes section Page 38 A8812 AcquiSuite Data Acquisition Server Shop for Power M...

Страница 39: ...5 clearance Two 1 2 holes are provided in the bottom of the AcquiSuite for wiring purposes The AcquiSuite has 4 mounting holes for use with a 6 or 8 screw The drawing above shows the relative position...

Отзывы: