Installation instructions
V20-...-550
OBO Bettermann GmbH & Co. KG
9
EN
Faults
If the integrated cut-off unit trips (e.g. due to age
on account of multiple, very high overvoltages),
the visual display (Figure ) switches from green
(grey) to red. In this case, remove the arrester
and insert a new arrester (available separately,
V20: item no. 5095 364, C20: item no. 5095 600).
In the case of devices with multiple arresters, it
must be assumed that the other arresters of this
device have experienced the same load. We rec-
ommend that you check them and, if necessary,
also replace them. Dispose of replaced arrest-
ers.
Remote signalling
Figure (only V20-..+FS..):
When at least one arrester is disconnected, the
changeover contact in the remote signalling mod-
ule switches from 11/12 to 11/14. Remote signal-
ling can be switched as an NO or NC contact.
This allows control of suitable signalling compo-
nents (e.g. central error messages, light or
acoustic signal).
• Connect the remote signalling cables as
shown, in so doing maintaining the specified
cable cross-section and the stripping length.
Maintenance
We recommend carrying out a visual check of
the visual display every 2-4 years or after light-
ning strikes.
Disposal
– Packaging as household waste
– Protection device/arrester as electronic waste.
Comply with the local waste disposal regulations.
Technical data
V20 ... 550
C20
IEC / DIN EN
61643-11
Class II / Type 2
U
C
550 V AC
255 V AC
U
N
500 V AC
230 V AC
U
P
≤ 2400 V
≤ 1300 V
U
res
@
1 kA
8/20
1600 V
–
5 kA
8/20
1900 V
–
I
imp
–
12 kA
I
n
20 kA
40 kA
I
max
40 kA
60 kA
I
SCCR
50 kA
eff
I
fi
-
100 A
IP code
IP 20 (built-in)
Number of
Ports
One-Port-SPD
System
TN-, TT
TN-, TT (NPE)
-40 – +80 °C
-40 – +176 °F
5 – 95 %
Protection
path
Protection
path
L – PEN
L – N
L – PE
N – PE
N – PE
x
x ≥ 1,5 mm (0.06 in)
F1
F2
+
F1 >160 A gL / gG
F2 ≤ 160 A gL / gG
– (NPE)
F1
F2
2
F1 ≤ 160 A
gL / gG
– (NPE)
1.5 – 35 mm
2
(AWG 16 – 2)
1.5 – 35 mm
2
(AWG 16 – 2)
1.5 – 35 mm
2
(AWG 16 – 2)
Accessories
a
a ≤ 15.5 mm (0.6 in)
5012 010
3 x 16 mm
2
(3 x AWG 6)
T1
T2