EN
13
– Installation as shown on wiring diagrams
7
IT system
8
IT system with neutral conductor
9
TN-C system
Error indication
If an error occurs as shown on fig .
2
, the device has
to be replaced .
Disposal
Dispose packaging as household waste, device as haz-
ardous waste (waste code no . 59101) . Comply with the
local waste disposal regulations .
Technical data
MCF 35-1+FS-440
SPD type acc . to EN 61643-11
Type I
LPZ
1 → 2
Max . continuous operating
voltage U
C
440 V AC / 50-60 Hz
Short circuit current rating I
SCCR
50 kA
Residual current I
PE
< 1 mA a .c .
Follow current interrupt rating I
fi
50 kA
Continuous operating current I
C
–
Voltage protection level U
P
≤ 2 .5 kV
TOV protection
760 V/5 s
Nominal discharge current In
35 kA (8/20)
Maximum discharge current I
imp
35 kA (10/350)